10
The following chart gives maximum series resistance:
Max. Series Resistance, Rs
Supply Voltage, Vs
1300 ohms
42.0 Volts
520 ohms
24.0 Volts
417 ohms
21.6 Volts
250 ohms
18.0 Volts
0 ohms
12.0 Volts
2.3.2 I
NPUT
T
ERMINALS
See Figure 5 for sensor input connections. Be certain to include the proper jumpers for
thermocouple sensors and for two or three wire RTD inputs. Any sensor other than the four-wire
RTD requires at least one external jumper. A jumper is supplied with the unit and is attached to
terminals 3 & 4.
Fig. 5
Input Terminal Connections
2.3.2.1 M
ILLIVOLT
AND
T
HERMOCOUPLE
I
NPUT
Apply signal to terminals 1 and 2. Terminal 1 is the negative and terminal 2 is the positive. Terminals
3 and 4 must be jumpered together for proper operation as well as to prevent any build-up of
electrostatic charge on these terminals which could affect the transmitter readings.
2.3.2.2 T
WO
-W
IRE
RTD I
NPUT
Apply signal to terminals 1 and 3. Jumpers must be installed on terminals 1 and 2 as well as on 3
and 4 for proper operation and to prevent any build-up of electrostatic charge on these terminals
which could affect the transmitter readings.
Содержание TX180
Страница 1: ...Model TX180 Temperature Transmitter Installation and Operation Manual P N 974083 04 02 Rev B ECO 26721...
Страница 2: ......
Страница 26: ...26 Fig 7 Dynisco TX180 ITX190 Configuration Flowchart LI 2 Two Line Display Keypad...
Страница 40: ...40 Fig 8 Dynisco TX180 ITX190 Configuration Flowchart LI 2 One Line Display Keypad...
Страница 50: ...NOTES...
Страница 52: ...DYNISCO INSTRUMENTS 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...