78
Lower display: CO.MAX
Range:
From 10.0 to 100.0%. This limit is active in manual and automatic mode.
Default value:
100.0
CONTROL OUTPUT MANUAL MODE INDICATION - Group 4
Available:
Always.
Upper display: Control output manual mode indication.
Lower display: CO.MMI
Range:
100.0 / rPn Use this parameter to select how the controller shows the output value
in manual mode; in the range 0-100.0%, or scaled with CO.RH and CO.RL
parameters (RPM indication).
Default value:
100.0
DIRECT/REVERSE SELECTION FOR CONTROL OUTPUT - Group 4
Available:
Always.
Upper display: Direct/reverse selection for control output.
Lower display: CO.D/R
Range:
r d, r r, d d, d r. The first digit shows the relationship between input signal and
displayed output value. The last digit shows the relationship between displayed
output signal and output value.
Example:
Value Signal
Input Output
Displayed Output
Control
r d
0 - 100 (increase)
100 - 0 (decrease)
100 - 0 (decrease)
r r
0 - 100 (increase)
100 - 0 (decrease)
0 - 100 (increase)
d d
0 - 100 (increase)
0 - 100 (increase)
0 - 100 (increase)
d r
0 - 100 (increase)
0 - 100 (increase)
100 - 0 (decrease)
Default value:
r d.
LINE FREQUENCY - Group 4
Available:
Always.
Upper display: Line frequency rejection.
Lower display: LINE.F
Range:
50, 60. 50 Hz. 60 Hz.
Default value:
50.
LOADING DEFAULT DATA - Group 4
Available:
Only if access to level c is allowed.
Upper display: OFF
Lower display: DEFLT
Содержание ATC770
Страница 19: ...ATC770 Microprocessor Based Pressure Process Controller 19 Fig 2 ATC770 Outline Drawing...
Страница 23: ......
Страница 30: ...30 Fig 6 Remote Set Point Jumper Location Board E...
Страница 84: ...NOTES...
Страница 85: ...NOTES...
Страница 86: ...NOTES...
Страница 88: ...DYNISCO INSTRUMENTS 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...