ATC770 Microprocessor-Based Pressure/Process Controller
75
REMOTE SET POINT INPUT FAIL SAFE - Group 4
Available:
Only if RI.TYP is different than OFF.
Upper display: Remote set point input fail safe condition.
Lower display: RI.IFS
Range:
HI, LO.
Default value:
Low.
ALARM 1 HYSTERESIS - Group 4
Available:
Only if A1.LNK is different than OFF.
Upper display: Alarm 1 hysteresis.
Lower display: A1.HYS
Range:
From 0.1 to 10.0% of the range.
Default value:
1.0%
ALARM 1 RESET MODE - Group 4
Available:
Only if A1.LNK is different than OFF.
Upper display: Selected reset mode for alarm 1.
Lower display: A1.RES
Range:
auto, LAtCh. Automatic reset, manual reset
Default value:
Auto.
ALARM 1 FAILSAFE MODE - Group 4
Available:
Only if A1.LNK is different than OFF.
Upper display: Selected failsafe mode for alarm 1.
Lower display: A1.FSM
Range:
FS, nFS. Failsafe mode, non-failsafe mode.
Default value:
Failsafe mode.
ALARM 2 HYSTERESIS - Group 4
Available:
Only if A2.LNK is different than OFF.
Upper display: Alarm 2 hysteresis
Lower display: A2. HYS
Range:
From 0.1 to 10.0% of the range.
Default value:
1.0%
ALARM 2 RESET MODE - Group 4
Available:
Only if A2.LNK is different than OFF.
Upper display: Selected reset mode for alarm 2.
Lower display: A2. RES
Содержание ATC770
Страница 19: ...ATC770 Microprocessor Based Pressure Process Controller 19 Fig 2 ATC770 Outline Drawing...
Страница 23: ......
Страница 30: ...30 Fig 6 Remote Set Point Jumper Location Board E...
Страница 84: ...NOTES...
Страница 85: ...NOTES...
Страница 86: ...NOTES...
Страница 88: ...DYNISCO INSTRUMENTS 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...