ATC770 Microprocessor-Based Pressure/Process Controller
45
6.5.1 S
ETTING
THE
S
ECURITY
C
ODE
FOR
L
EVEL
A
To view or change the security code, press the
FUNC
key and the lower display changes to
CODE.A. The upper display shows 0, which indicates no security, and 1 means all parameters
related to levels A, B, and C are always locked). Press the
▼
or
▲
keys until the desired security
code number (from 2 to 250) appears in the upper display. Press the
FUNC
key to lock in the value.
The upper display changes to
1, and the lower display changes to CODE.B. This means that ONLY
Levels B and C are locked, NOT Level A. If finished remove the instrument from its case and place
both dip switch SW1 and SW2 into the OFF position to return to the operating mode; otherwise,
continue with the next step.
6.5.2 S
ETTING
THE
S
ECURITY
C
ODE
FOR
L
EVEL
B
If you first set
CODE.A, the lower display will read CODE.B; if not, press the
FUNC
key to move to
CODE.B. The upper display shows 0, which indicates no security; or it may show 1, which means all
parameters related to levels A, B, and C are always locked). Press the
▼
or
▲
keys until the desired
security code number (from 251 to 500) appears in the upper display. Press the
FUNC
key to lock in
the value. The lower display changes to
CODE.C, and the Upper display shows 1. This means that all
levels are locked and cannot be changed. If finished, remove the instrument from its case and place
both dip switch SW1 and SW2 into the OFF position to return to the operating mode.
6.5.3 S
ETTING
THE
S
ECURITY
C
ODE
FOR
L
EVEL
C
If you first set
CODE.A and CODE.B, the lower display will read CODE.C. If not, press the
FUNC
key to move to
CODE.C. The upper display shows 0, which indicates no security; a 1 means all
parameters related to levels A, B, and C are always locked). Press the
▼
or
▲
keys until the desired
security code number (from 501 to 1000) appears in the upper display. Press the
FUNC
key to lock
in the value. The upper display changes to
CodE and the lower display changes to ATC. If finished,
remove the instrument from its case and place both dip switch SW1 and SW2 into the OFF position
to return to the operating mode.
Once the security codes are selected, they CANNOT be displayed. If the codes are forgotten, new
values must be entered using the above procedure. It is recommended that a code be set for each
security level. Note that unlocking the Level C code also unlocks Levels A, B, and C. To relock a
code, simply enter any incorrect number and all the locked levels will relock. Unlocking the Level B
code, unlocks Levels A and B. Unlocking Level A unlocks only Level A. When the
SECUR functions
are accessed in Group 1, the levels that are locked will be followed by a decimal point
7.
O
PERATION
7.1
P
RIMARY
I
NPUT
C
ALIBRATION
NOTE: In this section the word Calibration means to match the Instrument to the input device, so
Содержание ATC770
Страница 19: ...ATC770 Microprocessor Based Pressure Process Controller 19 Fig 2 ATC770 Outline Drawing...
Страница 23: ......
Страница 30: ...30 Fig 6 Remote Set Point Jumper Location Board E...
Страница 84: ...NOTES...
Страница 85: ...NOTES...
Страница 86: ...NOTES...
Страница 88: ...DYNISCO INSTRUMENTS 38 FORGE PARKWAY FRANKLIN MA 02038 ATTN MARKETING DEPT Place Stamp Here...