ATC770 Microprocessor-Based Pressure/Process Controller
29
5.4.1 S
ETTING
THE
R
EMOTE
S
ET
P
OINT
I
NPUT
V
OLTAGE
OR
C
URRENT
To change or view the Remote Set Point selection parameter, press the
FUNC
key until
nonE and
GROUP show on the display. Press the
▲
key until
5 shows in the upper display. Press the
FUNC
key until the lower display changes to
RI.TYP. Using the
▼
or
▲
keys, select the voltage or current
input desired: (0-10 VDC, 0-20 mA or 4-20 mA sources or
OFF). When finished, press the
FUNC
key to lock in the value. To select the jumper setting necessary, see Figure 5 below:
Fig. 5
ATC770 Board Location