26

NOTE: 

 The Invalid Code Counter will be reset every hour.

To disable the keypad lockout option, program the Number of
Invalid Codes Before Lockout as [000].

NOTE: 

 If  Keypad Lockout is active, the panel CANNOT be

armed / disarmed with a keyswitch.

Keypad Lockout Options. . . . . . . . . . . . . . . . . . Section [012]

5.22 Keypad Blanking

If the 

Blank Keypad When Not in Use

 option is enabled, the

panel will turn off all lights and LCDs on the keypads when no
keys are pressed for 30 seconds. The keys, however, will
remain backlit.
The panel will turn the lights and LCDs back on if entry delay
begins or an audible alarm occurs. The lights and LCDs will
also come on if a key is pressed or if a valid access code is
entered when the 

Code Required to Restore Blanking

option is enabled.

NOTE: 

If using a PC5132 v3.0 or higher, or PC5102 v1.0 or 

higher and wireless keys, do not enable the Code Required to
Restore Blanking option, as the keys will not function correctly.

If the 

Power Save Mode

 option is enabled the panel will blank

all keypad lights including backlighting when AC power fails,
in order to conserve the backup battery.

Blank Keypad when not in use . . . . . . . . .   Section [016]: [3] 
Code Required to Restore Blanking . . . . .   Section [016]: [4]
Power Save Mode . . . . . . . . . . . . . . . . . . .   Section [016]: [6]

5.23 Keypad Backlighting

The keys of all the keypads can be backlit to provide easy
viewing in dim lighting conditions. If the 

Keypad Backlighting

option is enabled the keys will be illuminated.

Keypad Backlighting Option . . . . . . . . . . . . Section [016]: [5]

5.24 Loop Response

The normal loop response time for all zones is 500 millisec-
onds. The panel will not consider a zone violated unless it is
violated for at least 500 milliseconds.
Zones 1-6 on the control board, however, can be programmed
for a fast loop response (under 40ms). 

Zones 1-6 are Fast Loop Response  . . . .  Section [030]: [1-6]

5.25 Keypad Tampers

If the 

Keypad Tampers Enable

 option is selected, the panel

will display and transmit a 

General System Tamper

 reporting

code if any keypad is removed from the wall. When the key-
pad tamper is restored, the panel will transmit the 

General

System Tamper Restoral

 reporting code. All keypads should

be properly installed and secured before enabling this option.

NOTE: 

The auto-arm cancellation code is not transmitted 

when a reset is required because a user has not cancelled the
auto-arming sequence.

Keypad Tamper Enable. . . . . . . . . . . . . . . . Section [016]: [8]
General System Tamper  and Tamper 
Restoral Reporting Codes . . . . . . . . . . . . . . . . . Section [338]

NOTE: 

After enabling keypad tampers, it is recommended that 

you tamper and restore all keypads to ensure proper function-
ing.

5.26 LINKS1000 Cellular Communicator

The LINKS1000 cellular communicator can be used three dif-
ferent ways:

as the sole communicator for the panel

as a backup for either or both telephone numbers

as a redundant backup to the land line communicator,
where the panel will call using the land line and the LINKS. 

A LINKS Preamble is programmable for each telephone num-
ber in the event that the land line number is local but the
LINKS is required to dial an exchange. When programming a
LINKS Preamble, all unused digits must be programmed with
a hexadecimal ‘F’.

NOTE: 

 If a LINKS1000 is connected to the system, make sure

the 

Maximum Number of Dialing Attempts

 is programmed to

be 008 or greater (section [160].

Using LINKS1000 as the Sole Communicator

The panel can be programmed to report an event using only
the LINKS1000 cellular communicator. To program this option,
select only the LINKS1000 in the 

Communicator Call Direc-

tion Options

. The 

Call LINKS as well as Land Line

 option

must also be enabled.
When the selected event occurs the panel will only attempt to
call central station using the LINKS.

Using the LINKS1000 as a Backup Communicator

The panel can be programmed to call using the LINKS1000
cellular communicator if the panel is having difficulty commu-
nicating an event using the land line. To program this option,
select both the telephone number and LINKS options in the

Communicator Call Direction Options

. The 

LINKS is

Backup of Land Lines

 option must be selected.

When used as a backup communicator, the panel will attempt
to call the central station in the following manner:
the panel will try to call using land lines – if unsuccessful, the
panel will try to call using the LINKS;
if unsuccessful, the panel will try to call using the land lines on
the next dialing attempt.
This process will continue until the panel has successfully
communicated with the central station or until the panel’s pro-
grammed number of dialing attempts has been exhausted.

Using the LINKS as a Redundant Communicator

The panel can be programmed to call using first the
LINKS1000 and then the land line when an event occurs. To
program this option, select both the telephone number and
the LINKS options for the 

Communicator Call Direction

Options

 for the event. The 

Call LINKS as well as Land Line

option must be selected.

LINKS Special Preamble

In some areas of North America, dialing #DAT or *DATA
reduces the cellular billing increment. The 

LINKS Special

Preamble

 (section [393]), allows the use of [*] and [#] charac-

ters for the programming of #DAT and *DATA.
The 

LINKS Special Preamble

 is sent BEFORE the Preamble

programmed in Sections [390] to [392].

Example:

  [Special Preamble][Regular Preamble][Telephone

Number]

NOTE: 

 If this Special Preamble is programmed, it will be

inserted before the Regular Preamble of ALL telephone num-
bers. Hex digits D and E are not supported for Preamble pro-
gramming.

NOTE: 

 If Busy Tone Detection is enabled, the LINKS1000

must be tested to ensure full operation.

Please refer to the LINKS1000 

Installation Manual

 for more

information and connection diagrams.

*Not investigated by UL

Содержание Power632

Страница 1: ...function and information on the limitations as to liability of the manufacturer The entire manual should be carefully read This panel will not operate if installed outside of North America See sectio...

Страница 2: ...a period of twelve months from the date of purchase the product shall be free of defects in materials and workmanship under normal use During the warranty period Digital Security Controls Ltd shall a...

Страница 3: ...booklet is available from the U S Gov ernment Printing Office Washington D C 20402 Stock 004 000 00345 4 IMPORTANT INFORMATION This equipment complies with Part 68 of the FCC Rules On the side of this...

Страница 4: ...ii PC1555MX Wiring Diagram LCD5500Z LCD5501Z PC1555RKZ LCD5501Z32 PC5502Z2 PC5506 PC5508Z PC5516Z PC5532Z SL 8...

Страница 5: ...imline 8 zone LED keypad All keypads have five programmable function keys Connect up to eight keypads 4 wire Quad connection to Keybus Built in piezoelectric buzzer Digital Communicator Specifications...

Страница 6: ...control Each output is individually programmable see 5 11 PGM Output Options See PC5208 Installation Instructions Sheet Escort5580 TC Module This Escort5580 TC module will turn any touch tone phone i...

Страница 7: ...sions 208mm x 115mm x 18mm 8 2 x 4 5 x 0 7 approxi mately 1 3 Out of the Box Please verify that the following components are included in your system one main control cabinet one PC1555MX main control...

Страница 8: ...ramming Worksheets completely before attempt ing to program the system Step 10 Testing the System Test the panel thoroughly to ensure that all features and func tions are operating as programmed 2 2 T...

Страница 9: ...ot connect the alarm panel communicator to telephone lines intended for use with a fax machine These lines may incorporate a voice filter which disconnects the line if anything other than fax signals...

Страница 10: ...twice to exit installer programming After assigning all keypads perform a supervisory reset by entering section 902 in Installer s Programming The panel will now supervise all assigned keypads and enr...

Страница 11: ...osed NC Loops To enable normally closed loops programming section 013 option 1 must be ON NOTE This option should only be selected if normally closed NC detection devices or contacts are being used Si...

Страница 12: ...e terminals on the keypad circuit board Connect the four Keybus wires from the control panel the red wire to R the black to B the yellow to Y and the green to G To connect the zone run one wire to the...

Страница 13: ...me every day if it is in the disarmed condition In order for the auto arm function to work properly you must program the cor rect time of day For programming the clock and auto arm times see 6 User Fu...

Страница 14: ...then restore power to the PC5204 and any connected modules This ensures that any troubles present on the module are correctly logged and or annunciated 2 AC Failure AC power is no longer being supplie...

Страница 15: ...l while other codes are silent To do this enable attribute 7 on all access codes associated with wireless keys NOTE If you enable the Bell Squawk on Arming Disarming section 014 option 1 the bell will...

Страница 16: ...Delay 3 5 Function Keys There are five function keys on each keypad labelled Stay Away Chime Reset and Exit Each of these keys is pro grammed by default to perform one of the functions described belo...

Страница 17: ...n 1 0 19 7 3 Command Output Option 3 A valid access code may need to be entered 20 For Future Use 21 7 4 Command Output Option 4 A valid access code may need to be entered 3 6 Features Available for t...

Страница 18: ...the section Select that section again and re enter the information correctly NOTE There must be one digit in each box in the program ming section in order for the change to be valid 4 2 Programming D...

Страница 19: ...wed from an LED key pad When a programming section is entered the keypad will immediately display the first digit of information programmed in that section The keypad displays the information using a...

Страница 20: ...pendently of Delay 1 in programming section 005 System Times 03 Instant Zone This zone type will cause an instant alarm if it is violated when the panel is armed Typically this zone is used for window...

Страница 21: ...to a LINKS Answer zone see 2 12 LINKS Zone Wiring Refer to the LINKS1000 Installation Manual for more information NOTE Do not wire LINKS Answer zones on keypad zone ter minals 25 Interior Delay Zone...

Страница 22: ...Tone Detection Section 701 6 Maximum Dialing Attempts Section 160 Post Dial Wait for Handshake Section 161 5 6 Communicator Account Numbers The account number is used by the central station to distin...

Страница 23: ...from transmitting an AC Failure Trouble Alarm reporting code during short power outages the panel will not send the signal unless AC power is lost for the amount of time programmed for the AC Failure...

Страница 24: ...he panel will operate as follows 1 If an event s reporting code is programmed as 00 or FF the panel will not attempt to call the central station 2 If the reporting code for an event is programmed as a...

Страница 25: ...er 8 Installer s Code 499 Installer s Code 499 All key pads will be busy for the duration of the PC Link connection The status LEDs will display the current system status on the keypad where the PC Li...

Страница 26: ...ill deacti vate if a user enters a valid access code while the bell cut off timer is counting down The output will also deactivate if someone arms the system after the bell cut off has expired This ou...

Страница 27: ...outputs PGM attributes return to their default settings when you change PGM output options Please see the Programming Worksheets for a list of the default settings for each PGM out put type Be carefu...

Страница 28: ...e times to verify activation The panel will beep the keypad ten times rapidly when a kissoff is received to verify communication to the central station If the P key is pressed and held for two seconds...

Страница 29: ...go into alarm If there was an alarm during the armed period the keypad will pulse for the entire entry delay to warn the user of the previous alarm For commercial applications Bell Squawk on Entry Del...

Страница 30: ...elephone numbers as a redundant backup to the land line communicator where the panel will call using the land line and the LINKS A LINKS Preamble is programmable for each telephone num ber in the even...

Страница 31: ...pro grammed Refer to your PC5132 v3 0 PC5102 v1 0 Installation Manual for more information NOTE The LINKS2X50 module has not been investigated by UL Restore Alternative Communicator LINKS2X50 Skyroute...

Страница 32: ...I PC5400 Serial Printer Module I________________________________________________________________________________________________________________I LINKS1000 Cellular Communicator I_____________________...

Страница 33: ...___I_____I_____I_____I_____I_____I_____I_____I_____I I_____I_____I I_____II_____II_____II_____II_____II_____II_____II_____I I_____I_____I_____I_____I_____I_____I Zone 17 I_____I_____I_____I_____I_____...

Страница 34: ...talled to use 24 hour Buzzer zones NOTE Keypad zones are assigned in section 020 Zone Attributes are assigned in sections 101 132 Zone assign ment is in sections 202 205 001 Zone 1 8 Definitions Secti...

Страница 35: ...___I_______I_______I Exit Delay in seconds Section 5 18 Entry Exit Delay Options 004 I_______I_______I_______I Bell Cut off in minutes Section 5 13 Bell 006 Installer s Code Section 4 1 Installer s Pr...

Страница 36: ...ors 2 11 ON I________I 3 Panel Shows All Troubles When Armed Panel Shows Only Fire Troubles When Armed 3 4 OFF I________I 4 Tampers Faults Do Not Show As Open Tampers Faults Show As Open 3 4 OFF I____...

Страница 37: ...pers Disabled 5 25 017 Fifth System Option Code Default Option ON Off Section ON I________I 1 WLS Key Does Not Use Access Codes WLS Key Uses Access Codes 5 17 OFF I________I 2 7 For Future Use OFF I__...

Страница 38: ...________I I________ I________ I________ I________ I________ I________ I________I 113 13 I________I I________ I________ I________ I________ I________ I________ I________I 114 14 I________I I________ I_...

Страница 39: ...________ I________I 131 31 I________I I________ I________ I________ I________ I________ I________ I________I 132 32 I________I I________ I________ I________ I________ I________ I________ I________I Re...

Страница 40: ..._____I_______I_______I Valid entries are 001 015 attempts do not enter 000 161 Post Dial Wait for Handshake All Formats Section 5 5 Communicator Dialing Default 040 I_______I_______I_______I Valid ent...

Страница 41: ..._I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I I_______I_______I 325 Zone 9 Zone 10 Zone 11 Zone 12 Zone 13 Zone 14 Zone 15 Zone16 I_______I_______I I____...

Страница 42: ...______I_______I I_______I_______I 343 Miscellaneous Closing Arming Reporting Codes Section 5 8 Communicator Reporting Codes Appendix A I_______I_______I 1 Closing by Duress Code 33 I_______I_______I 5...

Страница 43: ...ion 5 8 Communicator Reporting Codes Appendix A I_______I_______I 1 Wireless Device Low Battery Alarm I_______I_______I 2 Wireless Device Low Battery Restore 360 Communicator Format Options Section 5...

Страница 44: ...ay 001 255 seconds 5 15 030 I_______I_______I_______I AC Failure Communication Delay 001 255 minutes 5 8 003 I_______I_______I_______I TLM Trouble Delay No of checks required valid entries 003 255 5 1...

Страница 45: ...Downloading Default Option ON Off OFF I_______I 1 Answering machine double call enabled Answering machine double call disabled ON I_______I 2 User Can Enable DLS Window User Cannot Enable DLS Window O...

Страница 46: ...eypad LCD Keypad Bell Buzzer Good Light 1 ON Steady GOOD 1 Beep Squawk Bad Light 3 ON Steady BAD 3 Beeps Squawks 990 Installer Lockout Enable Section 5 29 Installer s Lockout 991 Installer Lockout Dis...

Страница 47: ...sion over the Keybus from enrolled PC5132 module or keypads with zone inputs A R 1 43 UA 00 UH 00 328 Cross Zone Police Code Alarm two zones on the same partition go into alarm during any given armed...

Страница 48: ...d MA R 4 54 CD 00 352 Periodic Test periodic system test transmission T 6 A2 RP 00 352 System Test 6 bell communications test T 6 A1 RX 00 352 LINKS Test LINKS test transmission T 6 A3 TX 00 353 Wirel...

Страница 49: ...e labels on page 29 33 Fire Alarm Label 14 Characters Default Fire Zone I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I_____I 34 System Label 14 Characters Default Syst...

Страница 50: ...I_______I 2 A uxiliary Keys Enabled A uxiliary Keys Disabled ON I_______I 3 P anic Keys Enabled P anic Keys Disabled OFF I_______I 4 8 For Future Use 65 Fourth User Display Mask Default Option ON OFF...

Страница 51: ...abled Closing confirmation must be enabled The control panel must be in the Attack Resistant Enclosure DSC Model CMC 1 PC4050CAR PC4004C Swinger shutdown must be disabled All Commercial Installations...

Страница 52: ...s Links2450 Yes Not investigated by UL PC 16 Out No PC1500RK No PC1555RKZ Yes PC5102 Yes PC5108 No PC5108L No PC5132 v1 X Yes No support for wireless keys pendants or handheld keypads PC5132 v2 X Yes...

Отзывы: