Section 5: Programming
[019] System Option 7
1 – Audible Wireless Device Fault
ON: If a wireless zone fault occurs while armed, the siren sounds for the duration of Bell Time Out. This option only affects
zone definitions that are considered armed. The following zone types do not generate an alarm when faulted while stay
armed: interior stay away zone, delay stay away zone, instant stay away zone, night zone. The following zone types do not
generate an audible alarm in any armed state (stay, away, or night): 24-hour supervisory, 24-hour non-alarm, 24-hour CO,
delayed 24-hour Fire, standard 24-hour fire, Auto-verified fire.
When the partition is armed, wireless supervisory troubles from sirens, keypads and repeaters generate audible alarm con-
ditions.
If Tamper/Fault Detection is enabled, these events can start the burglary verified timer and affect the burglary verified
counter.
OFF: Wireless device faults do not sound the siren.
2 – Latching Troubles
ON: Troubles remain on the system until viewed via [*][2], even if they are restored. The trouble condition is cleared when the
[#] key is pressed from the [*][2] menu after the trouble has restored. The Trouble LED turns off unless other troubles are
present. The trouble is not cleared if the [*][2] menu times out before the [#] key is pressed.
OFF: Troubles are cleared once restored.
3 – Not Used
4 – R Button
ON: When the panel goes off hook to communicate, it performs a dial tone check. If no dialtone is detected, the panel will
wait 20 seconds and perform another 5 second dial tone search. If dial tone is still not present, the panel force dials if pro-
grammed to do so. This entire sequence counts as one dialing attempt.
OFF: If no dial tone is present, the panel does not attempt to switch to a second phone line.
5 – Audible Bus Fault
ON: All module supervisory trouble conditions activate the siren.
OFF: Only zone expander supervisory trouble conditions while armed activate the siren.
6 – Duress Codes
ON: The duress code attribute can be enabled/disabled from the [*][5] menu. For
UK
BS8243 installations the default is off.
OFF: The duress code attribute is not programmable from the [*][5] menu.
7 – Temperature in Celsius
ON: Temperature is displayed in Celsius on LCD keypads.
OFF: Temperature is displayed in Fahrenheit on LCD keypads.
8 – Reset After Zone Activation
ON: Only a police code\sequential detection alarm requires a remote reset once the partition has been disarmed.
OFF: Any burglary alarm requires a remote reset once the partition has been disarmed.
[020] System Option 8
1 – Access Code Entry During Entry Delay
ON: During entry delay the alarm system can only be disarmed using a keyswitch or proximity tag. When the siren is active
an access code can still be used to disarm the system.
OFF: An access code can be used to disarm the system during entry delay.
2 – EU Entry Procedure
ON: If an alarm occurs on a zone when entry delay is not active, the siren activates and the alarm is communicated imme-
diately, depending on the zone type tripped.
When entry delay is active, all burglary type alarms activate the siren, but communication of the alarm is delayed by 30
seconds. When entry delay expires, the alarm is not communicated unless the siren has been active for at least 30 seconds.
Police code is not generated as a result of alarms triggered during entry delay, although the Burglary Verification Timer
starts after entry delay and the 30-second communication delay expire.
- 91 -