Appendix 4: Regulatory Approvals
The product is labeled with the UL and ULC listing marks along with the SIA CP-01 compliance statement (Also Classified in accordance with SIA-CP-01 Standard) as
proof of compliance with the above mentioned standards. For further information on this product’s listings please also refer to the official listing guides published at the
UL web site (www.ul.com) under Online Directions Section.
UL/ULC Residential Fire and Burglary Installations:
For ULC Installations refer to the Standard for the Installation of Residential Fire Warning Systems, CAN/ULC-S540.
l
All burglary-type zones shall be configured with SEOL or DEOL configuration. Use model EOLR-2.
l
(refer to section [002], bit 10 or 11 shall be ON)
l
Use at least one PG9926 or PG9916 Smoke Detector for Fire Installations (section [001], fire zone shall be programmed as type 025)
l
The entry delay shall not exceed 45 seconds (refer to section [005])
l
The exit delay shall not exceed 60 seconds (refer to section [005])
l
The minimum Bell Time-out is 4 minutes (refer to section [005])
Note:
For ULC Residential Fire Installations the minimum Bell Time-out is 5 minutes
For UL Home Health Care Installations the minimum Bell Time-out is 5 min.
For UL Commercial Burglary Installations minimum Bell Time-out is 15 min.
l
Temporal Three Fire Signal shall be enabled (section [013], opt.8 ON)
l
Arm/Disarm Bell Squawk shall be enabled when using wireless key PG4939, PG4929, PG4949 (section [014], option 1 shall be ON)
l
A code shall be required for bypassing (section [023], option 4 shall be ON)
l
Trouble beeps shall be enabled (section [022], option 7 shall be ON)
l
AC trouble indication LED shall be enabled (Keypad Programming, section [022], options 5 and 6 shall be ON)
l
DACT Communicator shall be enabled for Supervising Station Monitoring (section [380], option 1 shall be ON)
Note:
The DACT communicator for this product has no line security.
l
Telephone Line Monitoring (TLM) shall be enabled (section [015], option 7 shall be ON)
Note:
This product is programmed to perform 5 (min.) to 10 (max.) attempts for communication of an event to the supervising station. If unsuccessful, a Fail To Com-
municate (FTC) trouble is generated.
l
Test transmission cycle shall be set for monthly transmission (refer to section [351])
Note:
For ULC Residential/Commercial installations set for daily test transmission
l
Wireless Supervision window shall be set to 4 hours for Fire Installations (Wireless Programming, section [804]>[802] shall be programmed with the value
16)
l
Wireless Supervision window shall be set to 4 hours for Burglary Installations only (Wireless Programming, section [804]>[802] shall be programmed with the
value 96)
l
RF Jam detection shall be enabled (refer to Wireless Programming (section [804][801], option 00 shall be OFF)
l
New Alarms will Disconnect 2-way Audio (section [022], opt 6 OFF)
UL Central Station and Police Connect with Standard or Encrypted Line Security Service
l
The installation must use the Models TL2803G(R) IP/3G Interface, 3G2080(R) 3G Interface or TL280(R) IP Interface, which communicates over Cellular
Data Network or an Ethernet network 10/100BaseT to the compatible Sur-Gard System I/II/III/IV receiver.
l
Polling time shall be 200 seconds and compromise detection time shall be 6 min.
l
For Encrypted line security applications, the Models TL2803G(R) IP/3G Interface, 3G2080(R) 3G Interface or TL280(R) IP Interface shall have the Encryp-
tion Key enabled (AES128 bit encryption algorithm is validated under NIST Certificate No.2645
l
Wireless Supervision window shall be enabled (refer to Wireless Programming, sections [804]>[802])
UL Local, Central Station and Police Connect with No Line Security Service
l
The installation shall use a Bell which is UL Listed for Mercantile local alarms. An example of a UL Listed bell that can be used is Amseco Model MBL10B bell
with Model AB-12 bell housing. Connections from the control unit to the bell shall be made in conduit. (Optional for central Station)
l
The bell timeout shall be programmed for 15 minutes minimum
l
At least one system remote keypad with tamper switch shall be employed
l
The integral DACT shall be enabled and shall be programmed to provide a low battery transmission
l
The control panel shall be in the attack resistant enclosure. The separately listed CMC-1 or PC4050CA attack resistant enclosure shall be employed
l
The maximum entry delay time shall not exceed 45s as a result of the attack test. The maximum exit delay time shall not exceed 60 s.
l
A tamper switch shall be used to protect the enclosure cover of the control unit. A tamper switch shall also be used on the keypad rear to detect removal from
the wall.
l
24 h check in transmission shall be enabled
l
Open/Closing acknowledgement enabled.(Not Police Station)
l
The Installation shall use the internal dialer (DACT) alone or in conjunction with Models TL2803G(R) IP/3G Interface, 3G2080(R) 3G Interface or TL280(R) IP
Interface, which communicates over Cellular Data Network or an Ethernet network 10/100BaseT to the compatible Sur-Gard System I/II/III/IV receiver.
UL Home Health Care Signaling Equipment
l
There must be at least two keypads, one of either one of the compatible keypads models HS2LED, HS2LCD(P), HS2ICN(P), HS2LCDRF(P)9, HS2ICNRF
(P)9 and HS2TCHP
l
Each system shall be programmed to activate an audible Trouble signal within 90 seconds upon loss of microprocessor memory
l
The HS2TCHP shall be used along with another compatible model keypad in order to provide audible supervision for homehealth care or medical install-
ations.
ULC Central Station Fire and Burglary Monitoring Installations
l
For installation requirements, levels of security, communication modules and configurations (Refer to the ULC Installation Information Sheet, DSC
#29002157)
l
Use a CSA/cUL approved transformer (hardwired connections required for Fire Monitoring)
l
All tamper circuits may be connected to the same zone
l
HS2TCHP touch screen keypad is for supplementary use only with ULC Commercial Fire Monitoring
- 210 -