Appendix 4: Regulatory Approvals
In the UK this product is suitable for use in systems installed to conform to PD 6662:2010 at Grade 2 and environmental
class 2 with the following notification options: A, B, C, D, X.
The CIE and notification equipment should be located and supervised to minimize the risk of vandalism or sabotage. It is
preferable for the CIE, signaling and network equipment to be located in an area where a confirmed activation will be
generated.
HS2128, HS2064, HS2032, HS2016 are compliant with criteria for sequentially confirmed intruder alarm systems as per
Standard BS8243:2010.
For an alarm condition to be regarded as sequentially confirmed:
a) The HS2128, HS2064, HS2032, HS20163 should be configured so that at least two separate alarm conditions are
reported, each originating from an independent detector within the confirmation time; Section [042] option 003 (Sequential
Detection), section [005]>[000], Burglary Verification Timer set to a value between 30 and 60.
b) The two detectors should either be of:
1) different technologies which are permitted to have overlapping areas of coverage; or
2) the same single technology and not have overlapping areas of coverage.
To be regarded as independent, each detector should be configured to report alarm conditions separately to the HS2128,
HS2064, HS2032, HS2016.
The HS2128, HS2064, HS2032, HS2016 are capable of supporting the completion of the full setting procedure by one of the
following methods:
a) push button switch mounted outside the supervised premises. Instructions to be provided for the zone type to be
programmed for the key arming; or
b) protective switch (i.e., door contact) fitted to the final exit door of the alarmed premises or area. Use zone type 016 (Final
Door Set) for the final exit door.
In this case the setting procedure is a two-stage process of initiating the setting procedure within the supervised premises
(e.g., using wireless key PG8929,G8939, G8938, G8949 or user code) followed by completion of setting by one of the two
methods described above.
This prohibits the use of a timed exit procedure.
If a protective switch (i.e. door contact) is used as the method of completion of setting, then the keypad should be sited near
to the final exit door so that the IAS can be unset promptly. Where appropriate, additional internal audible indications
(PG8911 indoor sirens) should be provided so that persons within a building are informed that the HS2128, HS2064,
HS2032, HS2016 are due to be set. Additional keypads should be provided, where appropriate, so that if the alarm panel is
set there are means available locally within the supervised premises to unset the system.
HS2128, HS2064, HS2032, HS2016 are capable of supporting the following unsetting methods in accordance with BS8243:
6.4.2 Prevention of entry to the supervised premises before the HS2128, HS2064, HS2032, HS2016 are unset. Unsetting
using PG8929,G8939, G8938, G8949 wireless key before entering the supervised premises causes or permits the initial
entry door to be unlocked. Program PGM1 or PGM2 in Section [009] to activate when system is disarmed and release the
mag-lock on the entry door.
Compliance labeling should be removed or adjusted if non-compliant configurations are selected.