Section 2: Installation
See "[001] Zone Types" on page 64 for fire zone operation.
Note:
Smoke detectors must be latching type. To reset a smoke detector, enter [*][7][2].
Table 2-8 Compatible 4-Wire Smoke Detectors
FSA-410B
FSA-410BLST
FSA-410BRST
FSA-410BT
FSA-410BR
FSA-410BLRST
FSA-410BS
FSA-410BRT
FSA-410BST
FSA-410BRS
Current ratings for DSC FSA-410 Series: 25mA - 90mA
Fire Zone Wiring: 2-wire Smoke Detectors
If PGM 2 is programmed for 2-wire smoke detector connection, the detectors must be wired according to the following dia-
gram:
Figure 2-16 2-Wire Smoke Detector Wiring
Note:
Additional 2-wire smoke detectors must be connected in parallel as shown above. The maximum number of smoke
detectors on a 2-wire loop is 18.
Note:
Do not combine smoke detector models from different manufacturers on the same circuit. Operation may be impaired.
Refer to the smoke detector installation sheet when positioning detectors.
Table 2-9 Compatible 2-Wire Smoke Detectors
FSA-210B
FSA-210BR
FSA-210BT
FSA-210BRT
FSA-210BS
FSA-210BRS
FSA-210BST
FSA-210BRST
Current ratings for DSC FSA-210B series: 35mA - 75mA
Table 2-10 2-Wire Smoke Detector Initiating Circuit
Item
Specification
Style/Class, Supervised, Power Limited Style B (Class B)
Compatibility Identifier
HS2-1
DC Output Voltage
9.7-13.8 VDC
Detector Load
2mA (MAX)
Single End of Line Resistor (SEOL)
2200
Ω
Loop Resistance
24
Ω
(MAX)
Standby Impedance
3000
Ω
(NOM)
Alarm Impedance
1200
Ω
(MAX)
Alarm Current
86mA (MAX)
- 25 -