43
43
43
43
Connecting the roo
Connecting the roo
Connecting the roo
Connecting the room thermostat
m thermostat
m thermostat
m thermostat
In this type of configuration, a single room thermostat will be connected in inputs
27
27
27
27
and
29
29
29
29
(
TAF
TAF
TAF
TAF
Cooling thermostat) or in inputs
27
27
27
27
y
28
28
28
28
(
TAC
TAC
TAC
TAC
Heating thermostat). For this room thermostat
management configuration to work correctly, the heat pump should be configured for
a single
a single
a single
a single
operating mode, that is, Heating or Cooling (see
“Heat pump configuration”
) in the manual of
the
Dual Clima
heat pump. Depending on the input to which the thermostat is connected, it will
manage the corresponding mode of operation, and the type of room thermostat must be prepared
for this purpose. The thermostat connected to the cooling input (TAF) should demand (closed
circuit signal) when the room temperature is higher than the desired temperature (setpoint
temperature), and in turn, the thermostat connected to the heating input (TAC) should demand
(closed circuit signal) when the room temperature is lower than the desired temperature (setpoint
temperature).
Terminals
27
27
27
27
,
28
28
28
28
and
29
29
29
29
are supplied from the factory with a jumper wire connected to each of
them, so in order to install this type of thermostat, it will be necessary to remove
both
both
both
both
jumper wires
and connect the thermostat as described in the following figure, depending on the mode to be
managed:
Heating thermost
Heating thermost
Heating thermost
Heating thermostat (Heating Mode)
at (Heating Mode)
at (Heating Mode)
at (Heating Mode)
C
TAC
32
30 31
32
30 31
C
C
C
Cooling thermostat (Cooling
ooling thermostat (Cooling
ooling thermostat (Cooling
ooling thermostat (Cooling Mode)
Mode)
Mode)
Mode)
C
TAF
32
30 31
32
30 31
DANGER
DANGER
DANGER
DANGER When
When
When
When handling the electrical
handling the electrical
handling the electrical
handling the electrical installation, make sure that b
installation, make sure that b
installation, make sure that b
installation, make sure that both the module and
oth the module and
oth the module and
oth the module and
the Dual Clima heat pump are disconnected from the mains.
the Dual Clima heat pump are disconnected from the mains.
the Dual Clima heat pump are disconnected from the mains.
the Dual Clima heat pump are disconnected from the mains.
Содержание Fusion Hybrid Gas Condens
Страница 73: ...71 71 71 71 NOT NOT NOT NOTES ES ES ES ...
Страница 75: ...73 73 73 73 NOT NOT NOT NOTE E E ES S S S ...