141
ECLYPSE APEX
Parameter
Details
Maximum number of room devices
Subnetwork Module Compatibility and Supported Quantity Charts
also the Controller’s Datasheet.
Subnet ID Addressing Configuration
Setting the Subnet ID Addressing for Room Devices
Media
Cat 5e Patch Cable with RJ-45 Connectors (standard straight patch cable)
RJ-45 Pin Configuration
Four (4) pairs required. Straight-through wiring. Crimp connectors as per
T568A or T568B (both cable ends must be crimped the same way).
Characteristic impedance
100-130 Ohms
Distributed capacitance
Less than 100 pF per meter (30 pF per foot)
Maximum total length of the Cat 5e Cable
subnetwork data bus plus the 2-Wire
subnetwork data bus
300 m (1 000 ft.) Maximum – See
.
Maximum length of the Cat 5e Cable
subnetwork data bus for standard room devices
.
Maximum length of the Cat 5e Cable
subnetwork data bus for BLE room devices
.
Polarity
Polarity sensitive
Multi-drop
Daisy-chain (no T-connections)
Most room devices have two RJ-45 female pass-through connectors to
facilitate the daisy-chain connection of room devices.
For the EC-Multi-Sensor and EC-Multi-Sensor-BLE: An optional ECx-Subnet
Adapter (Y-splitter) is available to facilitate the daisy-chain connection of
room devices. The ECx-Subnet Adapter must be connected directly to the
EC-Multi-Sensor and its length cannot be extended.
EOL terminations
Must be set / enabled on the last room device only. This does not apply to
the ECx-Display.
Shield grounding
Not applicable
Table 21: Cat 5e Cable Subnetwork Data Bus Physical Specifications and Cable Requirements
Distech Controls recommends the Cat 5e cables shown below. Cables fitted with connectors are
crimped as T568B.
Cable Type
Non-Plenum Applications
(Use in Conduit - FT4)
Plenum Applications
(FT6)
Part Number
O.D. (Ø)
1
Part Number
O.D. (Ø)
1
0.3m (1 ft.), Cat 5e
Cable fitted with RJ-45
Connectors
CB-CAT5PC4WH0001
4.6mm (0.18in.)
CB-CAT5PC6WH0001
4.6mm (0.18in.)
4.6m (15 ft.), Cat 5e
Cable fitted with RJ-45
Connectors
CB-CAT5PC4WH0015
4.6mm (0.18in.)
CB-CAT5PC6WH0015
4.6mm (0.18in.)
9m (30 ft.), Cat 5e
Cable fitted with RJ-45
Connectors
CB-CAT5PC4WH0030
4.6mm (0.18in.)
CB-CAT5PC6WH0030
4.6mm (0.18in.)
15m (50 ft.), Cat 5e
Cable fitted with RJ-45
Connectors
CB-CAT5PC4WH0050
4.6mm (0.18in.)
CB-CAT5PC6WH0050
4.6mm (0.18in.)
22m (75 ft.), Cat 5e
Cable fitted with RJ-45
Connectors
CB-CAT5PC4WH0075
4.6mm (0.18in.)
CB-CAT5PC6WH0075
4.6mm (0.18in.)
30m (100 ft.), Cat 5e
Cable fitted with RJ-45
Connectors
CB-CAT5PC4WH0100
4.6mm (0.18in.)
CB-CAT5PC6WH0100
4.6mm (0.18in.)
300 m (1000 feet), Cat
5e Cable – Without
Connectors
CB-W244P-1446WHTB 4.6mm (0.18in.)
CB-W244P-2176WHTB 4.6mm (0.18in.)
100 Crimp RJ-45
Connectors
CB-W5506E
N/A
CB-W5506E
N/A
Table 22: Distech Controls Recommended Cable Types to use for the Cat 5e Cable Subnetwork Data Bus
1. Outer cable diameter – This does not take into account the RJ-45 connector.
Subnetwork Installation Guidelines