BACnet Settings
This is where the BACnet interface parameters are set.
General
This sets the controller’s BACnet network parameters.
Figure 42: General BACnet Settings
Item
Description
Controller Name
Set a descriptive name by which this controller will be known to other BACnet objects.
Device ID
Each controller on a BACnet intra-network (the entire BACnet BAS network) must have a unique
Device ID. Refer to the Network Guide for more information.
Location
Current controller’s physical location. This is exposed on the BACnet network as a device object
property.
Description
Description of the controller’s function. This is exposed on the BACnet network as a device object
property.
APDU Timeout (ms)
Maximum amount of time the controller will wait for an acknowledgment response following a
confirmed request sent to a BACnet device before re-sending the request again or moving onto the
next request. This property is exposed on the BACnet network as a device object property.
APDU Segment
Timeout (ms)
Maximum amount of time the controller will wait for an acknowledgment response following a
confirmed segmented request sent to a BACnet device before re-sending the segmented request
again or moving onto the next request. This property is exposed on the BACnet network as a device
object property.
APDU Retries
Sets the number of times to retry a confirmed request when no acknowledgment response has been
received. This property is exposed on the BACnet network as a device object property.
Export BACnet Object
List
Export all controller BACnet variables to a file (.csv).
Click to refresh the information in the list.
Apply
Click Apply to apply and save the changes