138
ECLYPSE APEX
Subnetwork Bus: Typical Connection for Room Devices
Cat 5e Cable Subnetwork Bus
Light or Sunblind
Expansion Module
Typical Room Devices
ECx-Subnet
Adapter
Allure Series
Sensors
ECx-Subnet
Adapter
ECx-Display
ECLYPSE APEX
Figure 112: Subnetwork Module Connection to the APEX Controller with an ECx-Display Connected as a Stub
Example
Subnetwork Data Bus Length
The maximum total length of the Cat 5e cable subnetwork data bus is 600 ft. (180 m) when using tra-
ditional Allure sensors, and 328 ft (100 m) when using BLE enabled Distech Controls devices.
600 ft (180 m) Maximum Length
Cat 5e Cable Subnetwork Bus
Light or Sunblind
Expansion Module
Typical Room Devices
ECx-Subnet
Adapter
Figure 113: Maximum Length of the Cat 5e Cable Subnetwork Data Bus with traditional Allure sensors
For traditional Allure Communicating Sensor models:
A controller can support a maximum of two (2) Allure series sensor models equipped with a CO
2
sen-
sor; the remaining connected models must be without a CO
2
sensor.
For instance, if the subnetwork for the controller model supports a subnetwork with 12 Allure series
communicating sensors in total, then 10 Allure series sensor models must be without a CO
2
sensor
and the remaining two (2) Allure series sensor models can be equipped with a CO
2
sensor. To ensure
proper operation, it is recommended to distribute the sensors throughout the length of the subnetwork.
Subnetwork Installation Guidelines
Содержание ECLYPSE APEX
Страница 1: ...User Guide ECLYPSE APEX...
Страница 171: ...ECLYPSE APEX_UG_11_EN...