130
ECLYPSE APEX
Description
Range
Example
BACnet/IP Network Number
0 to 65 534
1
ECLYPSE Controller BACnet/IP Device Instance Numbers: Multiples of 10 000 10 000 to 4 190 000
10 000
20 000
BACnet MS/TP Network Number: ECY Series Controller BACnet/IP Device
Instance Number/1000 + 0,1,2,3,4 (for each LAN)
10 to 4190
10
20
30
BACnet MS/TP Device Instance Number =
10 000 to 4 190 256 10 006 where MAC = 6
Table 16: Recommended Numbering Scheme for MAC Addresses, Instance Numbers, and Network Numbers
An example of this numbering system is shown below.
ECLYPSE
EOL
Externally
Set
END
EOL ON
ECLYPSE
EOL
Externally
Set
END
EOL ON
Figure 105: BACnet MS/TP Numbering System for MAC Addresses, Device Instance Numbers, and Network
Numbers
When discovering devices with EC-Net which has the routing option configured, it will discover all BACnet devices
connected to all ECY Series Controllers when routing is enabled (see
). Make sure to add only the devices
connected to the MS/TP port of the specific ECY Series Controller being configured. Using this numbering system will
greatly help to identify those devices that should be added to a given ECY Series Controller.
Setting the Controller’s MAC Address
The ECY Series Controller’s MAC address can be set in BACnet Settings of the
BACnet MS/TP Communication Data Bus Fundamentals