122
ECLYPSE APEX
Only a Daisy-Chained Data Bus Topology is Acceptable
Use a daisy-chained BACnet MS/TP data bus topology only. No other data bus topology is allowed.
Maximum of 32 nodes and 1200 meters.
Maximum is 50 nodes when using
Distech Controls devices exclusively
MS/ TP Data Bus Segment
Central Plant
Air Handling Controllers
Ethernet, TCP/IP, BACnet/IP, L
ON
W
ORKS
IP, XML, HTTP, oBIX
- Alarm
- Trend Log
- Schedule
EC-Net Supervisor
- Data Bus Management
- Data Bus Integration
- Device Configuration and
programming
- Graphical Interface
Configuration
EC-Net Pro
Web Browser
- User Interface
- Remote Access
- Embedded EC-Net Pro
Segment 1
EOL Internally Set to ON
EOL
ON
END EOL ON
ECLYPSE Controller
EOL Externally Set
Figure 93: Typical BACnet MS/TP LAN Topology Showing How Devices are Daisy-Chained Together to Form
One Data Bus Segment
Only linear, daisy-chained devices provide predictable data bus impedances required for reliable data bus operation.
Only a daisy-chained data bus topology should be specified during the planning stages of a project and implemented
in the installation phase of the project.
A spur is only permitted when it is connected to the data bus through a repeater (see
ECLYPSE
ECLYPSE
Figure 94: Unsupported BACnet MS/TP LAN Topologies
Data Bus Shield Grounding Requirements
The EIA-485 data bus standard requires that the data bus must be shielded against interference. A
BACnet MS/TP data bus must also be properly grounded.
For ECB Series 24V-Powered Controllers:
The data bus’ cable shields must be twisted together and isolated with electrical tape at each device.
Note that for ECB 24V-Powered Controllers, the power supply transformer’s secondary that is con-
nected to the 24V COM terminal is grounded. This provides the ground reference for the data bus (see
BACnet MS/TP is a Three-Wire Data Bus
). If the controller is at the end of the BACnet MS/TP data bus,
simply isolate the data bus shield with electrical tape.
BACnet MS/TP Communication Data Bus Fundamentals
Содержание ECLYPSE APEX
Страница 1: ...User Guide ECLYPSE APEX...
Страница 171: ...ECLYPSE APEX_UG_11_EN...