XTLplus Series Installation and Programming Guide | Digital Monitoring Products
55
False Alarm Reduction Programmable Options -
ANSI/SIA CP-01-2010
Shipping Defaults and Recommended Programming
SIA CP-01 DESCRIPTION
PROGRAMMING
SECTION
REQUIREMENT
RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
Exit Time
Exit Delay
Required
(Programmable)
45 sec. - 250 sec.
60 Seconds
60 Seconds
Progress Annunciation
Prewarn Address
Allowed
Individual keypads may
be disabled per zone
All keypads
enabled
All keypads enabled
Exit Time Restart
Exit Delay
Required Option
For re-entry during exit
time
Enabled
Enabled
Auto Stay Arm on Unvacated
Premises
Occupied Premise - See
Install Guide
Required Option (except
for remote arming)
Occupied Premise NO/
YES option
Enabled
Enabled Yes
for Residential
Applications
Exit Time and Progress
Annunciation/Disable - for
Remote Arm
Not Available on Remote
Arming
Allowed Option
Progress Annunciation
Always disabled for
Remote Arming
Not Available
Remote Arming not
allowed for CP-01
installations.
Entry Delay(s)
Entry Delay
Required
(Programmable) Only use
Entry Delay 1. Do not use
Entry Delay 2.
30 sec. – 240 Sec.
**
30 Seconds
At least 30 Seconds
**
Abort Window – for Non-Fire
Zones
Transmit Delay
Required Option
Disable by zone or
zone type
Enabled NT
DY EX Zone
Enabled
Abort Window Time – for
Non-Fire Zones
Transmit Delay
Required
(Programmable)
20 sec., 30 sec., or
40 sec.
**
30 Seconds
At least 20 Seconds
**
Abort Annunciation
Transmit Delay
Required Option
Annunciate that no
alarm was transmitted
Yes
Yes
Cancel Annunciation
Always Enabled - Not
Programmable
Required Option
Annunciate that a
Cancel was transmitted
(S49)
Always
Enabled
Yes
Duress Feature
User Code + 1 = Ambush
Code Not Available
Allowed Option
No 1 + derivative of
another user code/no
duplicates with other
user codes
Code +1
Always
Disabled
Not Programmable
Cross Zoning
Cross Zone
Required Option
Yes/No Zone
Programming
No
Enabled using two or
more programmed
zones
Programmable Cross Zoning
Time
Cross Zone Time
Allowed
4 sec. - 250 sec.
0 Seconds
Per walk path in
protected premises
Swinger Shutdown
Not Available - Always
On
Required
1-6 trips
2 trips
2 trips
Swinger Shutdown Disable
Swinger Bypass
Allowed
For non-police
response zones
Yes
Enabled (all zones)
Fire Alarm Verification
Zone Type
Required Option
FV Type Zone
No
Yes as required (unless
sensors can self verify)
System Test
Walk Test
Allowed
Test all protection
devices
N/A
N/A
Communications
Walk Test
Not Allowed
N/A
N/A
N/A
* Programming at installation may be subordinate to other listed requirements for the intended application.
** For listed Installations, combined Entry Delay and Transmit Delay should not exceed 1 minute.
Local Bell
All non-fire zones such as Night, Day, Exit, Aux 1 and Aux 2 must be programmed for local bell enabled with a bell cutoff time set to a minimum of 6
minutes to provide a cancel window of 5 minutes or greater. This does not apply to manually operated zone types such as Panic and Emergency.
The requirements are superseded by any requirements for Commercial Burglar, Household Fire Warning, or Household Burglar applications.
Minimum Installation Requirements: SIA CP-01-2010 minimum system installation requirements include an XTLplus, an 1135 Wireless Siren, a 9000
Series Wireless keypad, and communication to an SCS-1R receiver.