ALL WORKS CONCERNED WITH THE ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY SKILLED AND QUALIFIED PERSONNEL.
E
LECTRO
V
AP
RTH-V2
Wiring connections
ELECTRICAL CONNECTIONS
Failure to observe m anufacturer’s installation recommendations w ill invalidate the
m anufacturer’s w arranty.
3
2
L2
L1
N
L3
L
PE
RTH 5 to
100
Q1: 2 poles
2A
3 x 380V /
3 x 400V
50-60Hz
220-230V
50-60Hz
Q2: 3 poles
C) 3 neutral: 3 x 380-400 V
B) 3 X 380-400 V without neutral
L2
L1
N
L3
L
PE
RTH 5 to
100
3x380V
3x400V
50-60Hz
+ neutral
Q2: 4 poles
D) 3 phases without neutral: 3 x 380-400 V
In this case, a transformer (option) must be installed
(See technical notice page n°31)
All works concerned with electrical installation must be carried out by a skilled and qualified
personnel.
Make sure that all incoming power supplies are isolated before installation and maintenance of
the ElectroVap RTH humidifier.
1 - Power supply isolator and MCB ( near the unit )
2 - Power supply cable
3 - Electrical compartment
WARNING :
Failure to fit an electrical power isolator and MCB as part of
the electrical installation signif icantly increases the risk of
electric shock, which can be f atal.
Q1 and Q2: MCB and electrical power isolation
The symbol
∆
between Q1 & Q2 means that these
MCB are coupled. The power MCB Q2 and control
MCB Q1 are mechanically linked together. So if a
fault is detected, the power and the control circuits
are switched off and there is no voltage on the unit.
The unit is really off voltage.
1
A) 2 x 220-230V
L3
L2
L
N
PE
RTH 5
Q2: 2 poles
220 V / 230V
50-60Hz
L1
L
N
Install a differential electrical circuit breaker in head of the line supplying the humidifiers inside the general swichboard.
In case of several humidif iers, we would recommend to install a differential circuit breaker per humidif ier so as to
prev ent a total power cut off of all the humidif iers.