Pictures for illustrati ng pur poses o nly
28
RTH
Steam
production
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Puissance
(KW)
Nb of
boiler(s)
Nb of
heating
Power of
heating element
(KW)
7
7
575
3
5
5
1
3
1.9 (346V)
15
16
575
3
12
12
1
3
4.3 (346V)
20
23
575
3
17
17
1
6
3 x 1.9 (346V)
30
32
575
3
24
24
1
6
4.3 (346V)
40
39
575
3
29
29
1
9
6 x 4.3 (346V)
3 x 1.9 (346V)
50
47
575
3
36
36
1
9
4.3 (346V)
60
54
575
3
41
41
2
12
9 x 4.3 (346V)
3 x 1.9 (346V)
70
63
575
3
48
48
2
12
4.3 (346V)
80
77
575
3
59
59
2
18
12 x 4.3 (346V)
6 x 1.9 (346V)
90
86
575
3
65
65
2
18
15 x 4.3 (346V)
3 x 1.9 (346V)
100
95
575
3
72
72
2
18
4.3 (346V)
RTH steam humidifier in 3 x 575V - 50/60Hz
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Puissance
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating element
(KW)
7
8
600
3
6
6
1
3
1.9 (346V)
15
17
600
3
12
12
1
3
4.3 (346V)
20
25
600
3
16
19
1
6
3 x 1.9 (346V)
30
34
600
3
22
26
1
6
4.3 (346V)
40
42
600
3
27
32
1
9
6 x 4.3 (346V)
3 x 1.9 (346V)
50
51
600
3
33
39
1
9
4.3 (346V)
60
59
600
3
37
44
2
12
9 x 4.3 (346V)
3 x 1.9 (346V)
70
68
600
3
43
51
2
12
4.3 (346V)
80
84
600
3
53
63
2
18
12 x 4.3 (346V)
6 x 1.9 (346V)
90
93
600
3
59
70
2
18
15 x 4.3 (346V)
3 x 1.9 (346V)
100
103
600
3
65
78
2
18
4.3 (346V)
RTH steam humidifier in 3 x 600V - 50/60Hz
Beware ! Before connecting power, make sure that the electrical installation has been made
according to the above-mentioned values.
ALL WORKS CONCERNED WITH THE ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY SKILLED AND QUALIFIED PERSONNEL.
E
LECTRO
V
AP
RTH-V2
Electrical table