Pictures for illustrati ng pur poses o nly
17
A high humidity limit humidistat must be installed in the duct to stop the humidif ier in case the
lev el of humidity exceeds the preset value.
In case the recommended distances cannot be met, please contact
devatec
or their authorized
agent for an alternative solution.
If accurate v alues cannot be reached, a distance of 2 m. should be considered as a minimum
distance between pipes & obstruction and 3 / 4 m. before sensor or humidistat.
Before a junction
before an air opening
before a humidity sensor
D
D
5 x D
0,5 x D
Before / after a constriction
before an expansion
before a bend
D
0,5 x D
(CONTINUED)
E
LECTRO
V
AP
RTH-V2
Steam pipe positioning