Pictures for illustrati ng pur poses o nly
26
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Power
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating element
(KW)
5_3
6
415
3
6
4
1
3
1.9 (277V)
7
8
415
3
9
6
1
3
1.9 (230V)
10
13
415
3
14
10
1
3
4.3 (277V)
15
19
415
3
20
14
1
3
4.3 (230V)
20
26
415
3
27
19
1
6
4.3 (277V)
30
37
415
3
39
28
1
6
4.3 (230V)
40
46
415
3
48
34
1
9
6 x 4.3 (230V)
3 x 1.9 (230V)
50
56
415
3
59
42
1
9
4.3 (230V)
60
64
415
3
68
49
2
12
6 x 4.3 (230V)
6 x 4.3 (277V)
70
75
415
3
79
57
2
12
4.3 (230V)
80
91
415
3
96
69
2
18
12 x 4.3 (230V)
6 x 1,9 (230V)
90
101
415
3
107
77
2
18
15 x 4.3 (230V)
3 x 1.9 (230V)
100
112
415
3
118
85
2
18
4.3 (230V)
RTH steam humidifier in 3 x 415V - 50/60Hz
RTH
Steam
production
(kg/h)
Voltage (V)
Nb of
phase(s)
Amperage
(A)
Power
(KW)
Nb of
boiler(s)
Nb of
heating
element(s)
Power of
heating element
(KW)
7
6
440
3
6
5
1
3
1.9 (277V)
15
14
440
3
14
11
1
3
4.3 (277V)
20
21
440
3
20
15
1
6
3 x 1.9 (277V)
30
29
440
3
29
22
1
6
4.3 (277V)
40
35
440
3
35
27
1
9
6 x 4.3 (277V)
3 x 1.9 (277V)
50
43
440
3
43
33
1
9
4.3 (277V)
60
50
440
3
50
38
2
12
9 x 4.3 (277V)
3 x 1.9 (277V)
70
58
440
3
57
43
2
12
4.3 (277V)
80
71
440
3
70
53
2
18
12 x 4.3 (277V)
6 x 1.9 (277V)
90
79
440
3
78
59
2
18
15 x 4.3 (277V)
3 x 1.9 (277V)
100
87
440
3
86
65
2
18
4.3 (277V)
RTH steam humidifier in 3 x 440V - 50/60Hz
Beware ! Before connecting power, make sure that the electrical installation has been made
according to the above-mentioned values.
ALL WORKS CONCERNED WITH THE ELECTRICAL INSTALLATION MUST BE CARRIED OUT BY SKILLED AND QUALIFIED PERSONNEL.
E
LECTRO
V
AP
RTH-V2
Electrical table