Pictures for illustrati ng pur poses o nly
12
1. Use pref erably hose from our supply
NB : when brand new hoses are installed, a smell of burning may be smelt during the first running of the
steam humidifier. This is normal and will eventually dispel.
2. Number of steam outlets :
RTH 5 to 20 = 1 x
Ø
60 mm (
Ø
60 /
Ø
40 mm contriction union to consider, see after page n°14)
RTH 30 to 50 = 1 x
Ø
60 mm
RTH 60 to 100 = 2 x
Ø
60 mm
3. The RTH humidifier can be used with pressure ducts (P) having the f ollowing characteristics :
•
If P is inferior to 220mm CE (Water column) i.e. 2157 Pa.
•
If P is between 220mm CE and 370mm CE (3627 Pa.) , our optional filling cup plateform must be used.
4. Please adhere to the recommendations giv en underneath for the installation of the steam hose according to one of
the shown examples, the most suited to y our installation. A set of hose clamps is supplied f or ensuring a correct
installation.
Install the optional 300 mm long flexible steam hose sleeve(s) onto the steam tank outlet(s). Then with a 150 mm
long stainless steel (optional) union, join the
Ø
60 mm steam hose to this (these) sleeve(s). Make sure to keep the
steam hose still while connecting it to the sleeve(s). It is also possible to connect a stainless steel or copper
pipe to the sleev e(s).
The humidifier should be located within 3 m. of the steam distribution pipe. If the distance is superior to 3 m.
insulated steel or copper pipe of a slightly larger diameter must be used.
TAKE CARE : The steam hose must be kept as tight as possible. If it happens to be pinched or kinked, this can
cause the heating elements to ov erheat and to be destroy ed due to an incorrect detection of a too low water level
inside the cylinder.
Radius of bend f or steam hose :
- Ø
40mm steam hose = 400mm minimal radius
- Ø
60mm steam hose = 750mm minimal radius
E
LECTRO
V
AP
RTH-V2
Steam output
3 m m axi
5
0
0
m
m
m
in
i
Example a
Example b
5
0
0
m
m
m
in
i
3 m maxi
1
0
°
m
in
i
Ø60 mm stainless steel
union (option)
Keep the hose tight before
joining it to the sleeve(s).
70-90 ring clamp supplied
with the humidif ier
Ring bearing clamp
supplied with optional
stainless steel union.