30
4.4
Head Pressure Is Too High
POSSIBLE CAUSE
Insufficient system airflow
Excessive refrigerant charge
Non-condensables in system
Defective refrigeration valves
Restriction in refrigeration piping
REMEDY
1) Evaluate system airflow
(See Section 5.3.1.1)
2) Check for dirty air filters or
restricted ductwork.
3) Verify that coils are clean.
Re-evaluate system charge.
Evacuate or purge system.
Check 3-way, flooding, solenoid and
check valves for sticking.
1) Check coil and tubing for kinks.
2) Replace dirty drier filter.
1) Reduce entering air temperature or
relative humidity.
2) Check register locations for short
cycling of air.
REMOTE CONDENSER PROBLEMS WHICH CAUSE EXCESSIVE PRESSURES:
Lack of airflow
Remote condenser fan does not run.
Refrigeration system is overloaded
NOTE: LW SERIES DEHUMIDIFIERS
ARE DESIGNED FOR A MAXIMUM
RETURN AIR TEMPERATURE OF 70°F.
Assure remote condenser coil is
clean and no airflow restrictions exist
around unit.
A) Overload is a thermo protector.
Allow to cool to reset. If multiple
trips occur, verify amp draw and
replace motor if necessary.
A) Overload tripped
B) Contactor faulty
C) Blower cycling on internal protection
D) Controller settings
B) Replace contactor.
C) Reduce blower speed.
D) On models with a remote
condenser installed, verify that the
condenser is enabled.
A) Fully open service valves.
B) Re-evaluate remote condenser
installation.
Excessive pressure drop in line sets
NOTE: When the remote condenser is active and the outdoor temperature is
above 95°F, normal head pressure can be as high as 300 psig.