16
2.4
High Voltage Wiring
1.
Disconnect power before servicing. The unit contains high voltage wiring and
moving parts which may cause serious injury or death.
2.
Failure to properly wire the dehumidifier may create the possibility of shock and
can lead to premature system failure.
Electrical wiring must comply with all national, state, and local codes. Refer to the
wiring diagram located inside the electrical section for all wiring connections.
To connect main power, attach the supply wires to the three-pole power block for three
phase or two-pole power block for single phase units mounted on the electrical panel.
Test the phasing of the three phase unit by “bumping” the blower contactor.
Verify that the blower rotates in the proper direction. If it rotates the wrong direction:
•
Three-phase wiring: Switch any two of the three wires at the power block.
•
Single-phase wiring: The motor must be re-wired according to wiring diagrams
included with the motor.
2.4.1 High Voltage Connections
On single phase units the power supply must have 3 connections (2 power, 1
ground). On three phase units the power supply must have 4 connections
(3 power, 1 ground). Connect the power supply wires to the main power block
located in the upper section of the electrical compartment.
Figure 7 - Single-Phase and Three-Phase System Power Connection
Desert Aire - LW Manual