4.2. Compressor Will Not Run
POSSIBLE CAUSE
Controller settings
Loss of main power
Faulty wiring
Compressor overload has tripped
Comp. failure may have occurred if:
A) Comp. draws locked rotor amps
B) Comp. starts but does not pump
C) Motor windings have shorted
D) Incorrect rotation (reverse
phasing)
NOTE: THE LW SERIES DEHUMIDIFIER
IS DESIGNED FOR A MINIMUM
RETURN AIR TEMPERATURE OF 35°F.
If return air temperature drops below
32°F, an internal thermostat will trip
preventing the compressor from
activating. Operation below 32°F will
accelerate system wear-and-tear and
void the warranty.
REMEDY
A) Adjust controller set-points.
B) On models with a remote
condenser installed, verify that the
condenser is enabled.
Check for tripped circuit breaker or
blown fuses.
Check for loose or faulty wiring on
system and controller.
Inspect the following:
A) elevated head pressure
B) lack of oil to the compressor
C) locked rotor amps (LRA)
D) possible compressor failure
A) Replace compressor (or check
fuses on three-phase units).
B) Replace compressor.
C) Replace compressor.
Heat conditioned air to minimum 35°F.
Note that heating air will also reduce
relative humidity.
Desert Aire - LW Manual