23
•
Automatic Blower Operation
– the blower can be set to automatic or
continuous operation. Automatic operation will activate the blower on a call
for air dehumidification or air cooling (remote ready models only). The
blower will turn off when all set points are satisfied. Refer to the CM3540
Controller IO Manual for details.
3.3
Refrigeration Testing
Refrigeration based cooling systems are sometimes referred to as “sealed systems”.
This is in reference to the refrigeration system being hermetically sealed, no refrigerant can
leave the system and no contaminants are allowed inside. Factory equipment and procedures
ensure a clean and tight refrigeration system where only the specified refrigerant and oil are
in the system. This is a critical component to the longevity of the system.
Some Desert Aire systems are shipped in sections to allow for installation of some of the
sections in a location much different than another. An example is a unit with a remote
condenser ready circuit. The dehumidifier may be installed indoors near the conditioned
space while the remote condenser used to reject waste heat is located outdoors. The piping
of the condenser is completed in the field before the unit is commissioned. The design and
processing of the field piping is just as important as the factory piping in ensuring the
longevity of the system.
Selection of quality components, quality procedures, and full testing help to ensure the
sealed system failures are minimized wherever possible. Nonetheless, the mechanical
nature of many components creates some unforeseen wear and failure in certain instances.
Some units may need service at a point in the life of the product that requires opening the
hermetic refrigeration system. Special care must be taken to ensure that the system is
returned to service without contamination.
Whenever servicing Desert Aire equipment, observe the following:
•
Use only equipment rated for the pressures of the refrigerant being serviced.
•
Use only equipment dedicated to service of the refrigerant in the system. Do not use
equipment to service multiple refrigerant types.
•
Purge all hoses and equipment of non-condensable gasses before connecting to the
sealed system.
•
Use only original equipment parts or factory approved equivalent for servicing.
•
Use only refrigerant system oil.
•
Minimize the time the system is open to atmosphere while servicing. Cap all
connections when there is no active service work on the system. This is particularly
important with units that contain POE oils as moisture will be absorbed quickly and
cannot be removed with a vacuum.
Desert Aire - LW Manual