Evaporator Coil Does Not Fully Defrost
POSSIBLE CAUSE
Defrost cycle not working properly.
Faulty hot-gas bypass solenoid
Insufficient evaporator airflow rate
Lack of refrigerant
Restrictive filter drier
Defective expansion valve
Restriction in refrigeration piping
REMEDY
(See Section 3.2.3.1)
Replace if defective.
1) Evaluate system airflow.
(See Section 5.3.1.1)
2) Check for dirty filters or restricted
ductwork.
3) Assure coils are clean.
Re-evaluate system charge.
Evaluate filter pressure drop and
replace if necessary.
Evaluate expansion valve performance
and replace if necessary.
1) Check coil for kinks in tubing.
2) Evaluate debris in distributor.
NOTE:
The LW series dehumidifier is NOT intended for use below 32° F ambient air
temperatures. Running the system below 32° F will cause safety devices to shut down
the unit.