Troubleshooting
Although Desert Aire dehumidifiers have been designed for reliable and trouble-free operation, you
may occasionally encounter a service-related problem. If you cannot immediately diagnose and fix
the problem, do not be intimidated by the apparent complexity of the dehumidifier. Your common
sense and experience can help you solve the majority of these problems.
These problems or complaints are frequently caused by improper interlocks between the dehumidifier
and the other equipment and accessories at the jobsite. You may need to consult with other
contractors who have worked on different portions of this project.
The following list will help you diagnose some of the most obvious symptoms of a system which does
not work properly.
4.1
Supply Blower will Not Run
POSSIBLE CAUSE
System terminal switch in open
position
Loss of main power
Blower overload relay or thermal
overload has tripped.
Blown fuse in electrical circuit
Defrost mode
REMEDY
Close system terminal switch.
Check for tripped circuit breaker or
blown fuses.
Check blower amp draw and reset
overload. Thermal protector or
thermal overload will auto reset once
motor has cooled.
NOTE: Problem may be electrical or
excessive system airflow
(see Section 5.3.1.1).
Check for blown fuses
Cycle power