Chapter 2 Installation and Wiring
|
VFD-VL
2-12
Terminal symbols and functions
Terminal
Symbol
Terminal Function
Factory Settings (SINK)
ON: Connect to DCM
FWD Forward-Stop
Command
ON:
RUN in FWD direction
OFF:
Stop acc. to Stop Method
REV Reverse-Stop
Command
ON:
RUN in REV direction
OFF:
Stop acc. to Stop Method
MI1
Multi-function Input 1
MI2
Multi-function Input 2
MI3
Multi-function Input 3
MI4
Multi-function Input 4
MI5
Multi-function Input 5
MI6
Multi-function Input 6
MI7
Multi-function Input 7
MI8
Multi-function Input 8
Refer to Pr.02-01 to Pr.02-08 for programming
the Multi-function Inputs.
ON: input voltage is 24Vdc (Max. 30Vdc), input
impedance is 3.75k
Ω
OFF: leakage current tolerance is 10
μ
A.
MI8: when JP1 is inserted, this function is
disabled.
COM
Digital Signal Common
Common for digital inputs and used for SINK
mode
+E24V
Digital Signal Common
(Source)
+24V 80mA
DCM
Digital Signal Common (Sink)
Common for digital inputs and used for SINK
mode
RA
Multi-function Relay Output 1
(N.O.) a
RB
Multi-function Relay Output 1
(N.C.) b
RC Multi-function
Relay
Common
MRA
Multi-function Relay Output 2
(N.O.) a
MRC Multi-function
Relay
Common
Resistive Load:
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Inductive Load:
1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
To output monitor signal, including in operation,
frequency arrival, overload and etc.
Refer to Pr.02-11~02-12 for programming
+10V
-10V
Potentiometer Power Supply
-10~+10VDC 20mA (variable resistor 3-5kohm)
MCM
Multi-function Output
Common (Photocoupler)
Max. 48VDC 50mA