Appendix B Accessories
|
VFD-VL
B-12
460V, 50/60Hz, 3-Phase
Inductance (mH)
kW HP
Fundamental
Amps
Max.
continuous
Amps
3% impedance
5% impedance
5.5
7.5
18 27 1.5
2.5
7.5
10
18 27 1.5
2.5
11
15
25 37.5 1.2
2
15
20
35 52.5 0.8
1.2
18.5
25
45 67.5 0.7
1.2
22
30
45 67.5 0.7
1.2
30
40 80
120
0.4
0.7
37
50 80
120
0.4
0.7
45
60 100
150
0.3
0.45
55
75 130
195
0.2
0.3
75
100 160
240
0.15
0.23
B.4.3 Applications for AC Reactor
Connected in input circuit
Application 1
Question
When more than one AC motor drive is
connected to the same power, one of them
is ON during operation.
When applying to one of the AC motor
drive, the charge current of capacity may
cause voltage ripple. The AC motor drive
may damage when over current occurs
during operation.
Correct wiring
M1
M2
Mn
reactor
AC motor drive
AC motor drive
AC motor drive
motor
motor
motor
Call 1(800)985-6929 for Sales