Chapter 4 Parameters
|
VFD-VL
4-90
07-28
Emergency Stop (EF) & Forced Stop Selection
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory
Setting:
0
Settings
0
Coast
to
stop
1 By deceleration Time 1
2 By deceleration Time 2
3 By deceleration Time 3
4 By deceleration Time 4
5
By
Pr.01-31
When the multi-function input terminal is set to 10 or 14 and it is ON, the AC motor drive will be
operated by Pr.07-28.
07-29
Time for Decreasing Torque at Stop
Control
mode
FOCPG
TQCPG
FOCPM
Factory
Setting:
0.000
Settings
0.000 to 1.000 sec
When the elevator is stop and the mechanical brake is engaged, the drive will stop output. At
the same time, it will produce the noise from the reacting force between the motor and the
mechanical brake. This parameter can be used to decrease this reacting force and lower the
noise.
It is used to set the time for decreasing torque to 0%.
RUN/STOP
0%
i
t
i
00-01 x
100%
300% x (07-29)=t