Chapter 4 Parameters
|
VFD-VL
4-80
It is used with the setting 43 (EPS function) of Pr.02-01~02-08 (Multi-Function Input
Command).
06-31
Phase Loss Detection of Drive Output at Start-Up(MPHL)
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings
0
Disable
1
Enable
When it is set to 1, it will auto detect if the connection between the drive and motor is normal
whenever the drive runs. If errors occur to the connection between the drive and the motor, the
drive will display fault code “67” to indicate motor output phase loss.
06-32
Accumulative Drive Power-on Time at the First Fault (min.)
06-34
Accumulative Drive Power-on Time at the Second Fault (min.)
06-36
Accumulative Drive Power-on Time at the Third Fault (min.)
06-38
Accumulative Drive Power-on Time at the Fourth Fault (min.)
06-40
Accumulative Drive Power-on Time at the Fifth Fault (min.)
06-42
Accumulative Drive Power-on Time at the Sixth Fault (min.)
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings
00 to 1439 min
06-33
Accumulative Drive Power-on Time at the First Fault (day)
06-35
Accumulative Drive Power-on Time at the Second Fault (day)
06-37
Accumulative Drive Power-on Time at the Third Fault (day)
06-39
Accumulative Drive Power-on Time at the Fourth Fault (day)
06-41
Accumulative Drive Power-on Time at the Fifth Fault (day)
06-43
Accumulative Drive Power-on Time at the Sixth Fault (day)
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings
00 to 65535 day
06-44
Operation Speed of Emergency Power Mode
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0.00
Settings
0.00 to 400.00Hz