Chapter 4 Parameters
|
VFD-VL
4-11
4.1.7 Group 6 Protection Parameters
Pr.
Explanation
Settings
Factory
Setting
VF
VFPG
SVC
FO
CPG
TQ
CPG
FO
CP
M
160.0~220.0Vdc 180.0
○ ○ ○ ○ ○ ○
06-00 Low Voltage Level
320.0~440.0Vdc 360.0
○ ○ ○ ○ ○ ○
06-01 Phase-loss Protection
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
2
○ ○ ○ ○ ○ ○
06-02 Over-current Stall
Prevention during
Acceleration
00: disable
00~250%
00
○ ○ ○
06-03 Over-current Stall
Prevention during Operation
00: disable
00~250%
00
○ ○ ○
06-04 Accel./Decel. Time Selection
of Stall Prevention at
constant speed
0: by current accel/decel time
1: by the 1st accel/decel time
2: by the 2nd accel/decel time
3: by the 3rd accel/decel time
4: by the 4th accel/decel time
5: by auto accel/decel time
0
○ ○ ○
06-05 Over-torque Detection
Selection (OT1)
0: disable
1: over-torque detection during constant speed operation,
continue to operate after detection
2: over-torque detection during constant speed operation, stop
operation after detection
3: over-torque detection during operation, continue to operate
after detection
4: over-torque detection during operation, stop operation after
detection
0
○ ○ ○ ○ ○ ○
06-06 Over-torque Detection Level
(OT1)
10~250% 150
○ ○ ○ ○ ○ ○
06-07 Over-torque Detection Time
(OT1)
0.0~60.0 sec
0.1
○ ○ ○ ○ ○ ○
06-08 Over-torque Detection
Selection (OT2)
0: disable
1: over-torque detection during constant speed operation,
continue to operate after detection
2: over-torque detection during constant speed operation, stop
operation after detection
3: over-torque detection during operation, continue to operate
after detection
4: over-torque detection during operation, stop operation after
detection
0
○ ○ ○ ○ ○ ○
06-09 Over-torque Detection Level
(OT2)
10~250% 150
○ ○ ○ ○ ○ ○
06-10 Over-torque Detection Time
(OT2)
0.0~60.0 sec
0.1
○ ○ ○ ○ ○ ○
06-11 Current Limit
0~250%
200
○ ○ ○
06-12
Electronic Thermal Relay
Selection
0: Inverter motor
1: Standard motor
2: Disable
2
○ ○ ○ ○ ○ ○
06-13 Electronic Thermal
Characteristic
30.0~600.0 sec
60.0
○ ○ ○ ○ ○ ○
06-14 Heat Sink Over-heat (OH)
Warning
0.0~110.0
℃
85.0
○ ○ ○ ○ ○ ○
06-15 Stall Prevention Limit Level 0~100% (refer to Pr.06-02, Pr.06-03)
50
○ ○ ○
06-16 Present Fault Record
0
○ ○ ○ ○ ○ ○
06-17 Second Most Recent Fault
Record
0
○ ○ ○ ○ ○ ○
06-18 Third Most Recent Fault
Record
0
○ ○ ○ ○ ○ ○
06-19 Fourth Most Recent Fault
Record
0
○ ○ ○ ○ ○ ○
06-20 Fifth Most Recent Fault
Record
0
○ ○ ○ ○ ○ ○
06-21 Sixth Most Recent Fault
Record
0: No fault
1: Over-current during acceleration (ocA)
2: Over-current during deceleration (ocd)
3: Over-current during constant speed (ocn)
4: Ground fault (GFF)
5: IGBT short-circuit (occ)
6: Over-current at stop (ocS)
7: Over-voltage during acceleration (ovA)
8: Over-voltage during deceleration (ovd)
9: Over-voltage during constant speed (ovn)
10: Over-voltage at stop (ovS)
0
○ ○ ○ ○ ○ ○