Chapter 4 Parameters
|
VFD-VL
4-69
It is used to set the accel./decel. time selection when stall prevention occurs at constant speed.
06-05
Over-torque Detection Selection (OT1)
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings
0
Over-Torque detection disabled.
1
Over-torque detection during constant speed operation, continue to
operate after detection
2
Over-torque detection during constant speed operation, stop
operation after detection
3
Over-torque detection during operation, continue to operate after
detection
4
Over-torque detection during operation, stop operation after
detection
06-06
Over-torque Detection Level (OT1)
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 150
Settings
10 to 250%
06-07
Over-torque Detection Time (OT1)
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0.1
Settings
0.0 to 60.0 sec
06-08
Over-torque Detection Selection (OT2)
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 0
Settings
0
Over-Torque detection disabled.
1
Over-torque detection during constant speed operation, continue to
operate after detection
2
Over-torque detection during constant speed operation, stop
operation after detection
3
Over-torque detection during operation, continue to operate after
detection
4
Over-torque detection during operation, stop operation after
detection
06-09
Over-torque Detection Level (OT2)
Control
mode
VF
VFPG
SVC
FOCPG TQCPG FOCPM
Factory setting: 150
Settings
10 to 250%