Chapter 4 Parameters
|
VFD-VL
4-112
These two parameters are used to decide width of slope of ASR command during zero speed
to low speed or Pr.10-17 to high speed.
10-17
10-13
10-14
10-15
10-16
Hz
PI
10-11
10-12
0Hz
10-20
10-21
10-22
Zero Speed Position Holding Time
Control
mode
FOCPM
Factory
Setting:
0.250
Settings
0.001
to
65.535sec
10-23
Filter Time at Zero Speed
Control
mode
FOCPM
Factory
Setting:
0.004
Settings
0.001
to
65.535sec
10-24
Time for Executing Zero Speed
Control
mode
FOCPM
Factory
Setting:
0
Settings
0
After the brake release set in Pr.02-29
1
After the brake signal input (Pr.02-01~02-08 is set to 42)
When Pr.10-24=0, the zero speed control needs to be used with Pr.02-29. (refer to the
explanations in Pr.02-32)
10-25
Elevator Leveling (Zero Speed Gain P)
Control
mode
VF VFPG SVC
FOCPG FOCPM
Factory Setting: 0
Settings
0~1000.0%
10-26
Elevator Leveling (Zero Speed Integral I)
Control
mode
VF VFPG SVC
FOCPG FOCPM
Factory Setting: 0
Settings
0~10.000
sec