ERROR
Message
Code
Cause
Action
AC Volt High Grid voltage over the limit of
electricity regulation.
Check the grid voltage.
If grid voltage is not in acceptable range,
ask the utility operator to modify it.
If grid voltage lies in acceptable range but
the error still exist, please contact your
inverter supplier.
E13
Solar1 High DC1 voltage > 600V
(more than 0.1s)
Disconnect the DC1 input and check the
PV array voltage.
If the PV array voltage still over 600V,
please contact the PV array supplier.
If the PV array voltage is fine but the error still
exist, please contact your inverter supplier.
E30
Solar2 High DC2 voltage > 600V
(more than 0.1s)
Disconnect the DC2 input and check the
PV array voltage.
If the PV array voltage still over 600V,
please contact the PV array supplier.
If the PV array voltage is fine but the error still
exist, please contact your inverter supplier.
E31
Insulation
PV array impedance in either
input < 550 kohm
Check the insulation of DC input wiring.
Check the string for ground faults.
If the insulation of DC wiring is fine but the
error still exist, please contact your inverter
supplier.
E34
Table 7-1 : Error Message
52
Error message and Trouble Shooting