Communication Module has 1 set of emergency power off function (EPO).
When the VCC and INV OFF pins are short-circuited, inverter will shut down
immediately. The module also provides 6 sets of digital input function (K1~K6).
Please refer to
Table 4-7
for the digital input definition. The suitable electric wire
is 30-16AWG.
In Australia and New Zealand, the Demand Response Modes (DRMs) are
also use digital input function to assert. The definition is different from normal
digital input function; please refer to
Table 4-8
for the DRMs pin definitions.
4.8 Digital Input / DRM & EPO Functions
Short
Inverter’s action
VCC & INV OFF
Emergency power off (EPO)
VCC & K1
0% active power
VCC & K2
Maximum 30% active power
VCC & K3
Maximum 60% active power
VCC & K4
Maximum 100% active power
VCC & K5
Reserved
VCC & K6
Reserved
Table 4-7 :
Definition of digital input & EPO functions
Short
Inverter’s action
VCC & INV OFF
DRM 0 (Disconnect from grid)
VCC & K1
DRM 5 (0% generate power)
VCC & K2
DRM 6 (50% generate power)
VCC & K3
DRM 7 (75% generate power and sink reactive power)
VCC & K4
DRM 8 (100% generate power)
VCC & K5
Reserved
VCC & K6
Reserved
Table 4-8 :
Definition of DRMs for Australia and New Zealand
Communication Module has 1 set of Dry Contact. The trigger condition of this
function can be customized by Installer. When the function is triggered, the output
two ports will be short-circuited. Please refer to section
5.3.8 Install Settings
for
more details about trigger condition assignation.
4.9 Dry Contact Connection