If it is necessary to put the device out of operation for maintenance or storage,
please follow the procedures below:
At inverter side:
1. Switch off the AC/DC switch and wait for display turning off.
2. Switch the manual bypass switch to normal.
3. Wait for E5’s display panel and battery box’s LED indicator light off.
At wiring side:
4. Switch off AC power line breaker to disconnect from grid.
5. Switch off DC power line breaker to disconnect from PV array.
6. Use proper voltmeter to check that the AC and DC power are truly disconnected.
7. Remove the AC, DC, and battery wiring.
8. Remove the communication module RS-485 connection from the computer
connection.
Now you may unload the inverter.
8 De-Commissioning
WARNING !
- To avoid injuries, please follow the procedures to unload the inverter.
55
De-Commissioning