- Make sure to use the proper size of AC cable.
- Please choose the terminals as shown in
Figure 4-3
for wires crimping.
- Failed to follow these instructions may cause AC plug damage.
CAUTION
!
Machine and equipment damage may occur.
Figure 4-3 : Terminal for wire crimping
The AC wiring system diagram is shown in
Figure 4-3
. It recommended users
follow the diagram connecting the AC wiring. The connection between Grid N
and Load N is used to eliminate the floating voltage between Load N and PE.
E5 can still works without the Grid N and Load N connection.
4.2.3 AC Plug Assembly
Follow the steps below to strip the wires before assembling the AC plug as
shown in
Figure 4-4
:
• Remove 55 mm (2.2 inch) of AC cable outer jacket.
• Trim the L-N(Grid), L-N(Load) wire to 52.5 mm (2.0 inch).
• Strip 10 mm (0.5 inch) of insulation from all wires ends.
• Crimp terminals for all wires.
Figure 4-4 : Striping the wires
outer jacket
12 mm
[0.5 in.]
52.5 mm
[2.0 in.]
55 mm [2.2 in.] (PE)
21
Wiring