- The settings in Install Settings page can only be adjusted by qualified installers or
engineers. Changing these settings may result in damage to the inverter and other
equipment.
CAUTION !
5.3.8 Install Settings
Install Settings page is for installer only.
To enter this page, installer has to key in installer password.
The page includes following functions :
Inverter ID is used to recognized the inverter when you communicating with
it via RS-485.
• Inverter ID
Inverter will measure the impedance between PV array and PE before
connecting to grid. To avoid risk of electrical shock, it’s not recommending to
disable this function.
• Insulation
Each country has its own electricity regulations. The hybrid inverter can meets
more than one electricity regulations. Installer must select the country correctly.
• Country
Installer can choose the trigger condition of dry contact. The explanations of
these conditions are shown in following table.
• Dry Contact
This option is used to clear the battery power fault message. Before clearing
the fault message, please make sure the battery has been repaired.
• Clear BT PF
Setting
Dry Contact Trigger Timing
Disable
No action.
On Grid
Inverter is connecting to grid.
Insulation
Insulation test fail.
Alarm
Any error or fault occurs.
Any fault occurs.
Table 5-2 : Dry contact trigger condition
Error
Any error occurs.
Fault
This function is currently used in Germany only. Installer in Germany should
set the PV array capacity and enable this function. The maximum feed-in power
to grid will be limited at a percentage of PV array capacity. Installers can set
the various limit percentage to meet the local electricity regulation.
• Subsidy Function
48
Turning On the Hybrid Inverter