5 - 7
5 Installation and Wiring
DPH Series 200 ~ 600kVA
UPS Capacity
200kVA/
200kW
300kVA/
300kW
400kVA/
400kW
500kVA/
500kW
600kVA/
600kW
Input
Maximum Cable
lug width
50 mm (1.97”)
Screw size/
Cable lug inner
diameter
M12/ 13 mm (0.51”)
Terminal type*
1
TLAPH325-2A12
Bypass
&
Output
Rated current at
voltage 220V
303A
455A
606A
758A
909A
Recommended
cable size (L1/
L2/ L3/ N)
70 mm
2
× 2 PCS
(3/0 AWG
× 2 PCS)
150 mm
2
× 2 PCS
(300 kcmil
× 2 PCS)
240 mm
2
× 2 PCS
(500 kcmil
× 2 PCS)
185 mm
2
× 3 PCS
(400 kcmil
× 3 PCS)
240 mm
2
× 3 PCS
(500 kcmil
× 3 PCS)
Maximum cable
size (L1/ L2/
L3/ N)
300 mm
2
× 3 PCS
(600 kcmil × 3 PCS)
Maximum cable
lug width
50 mm (1.97”)
Screw size/
Cable lug inner
diameter
M12/ 13 mm (0.51”)
Terminal type*
1
TLAPH325-2A12
Battery
Nominal
discharge
current
(condition:
12V × 40 PCS)
440A
660A
880A
1100A
1320A
Maximum
discharge
current
(condition: 9.6V
× 40 PCS)
549A
823A
1097A
1371A
1645A
Recommended
cable size
(+/ -/ N)
150 mm
2
× 2 PCS
(300 kcmil
× 2 PCS)
300 mm
2
× 2 PCS
(600 kcmil
× 2 PCS)
240 mm
2
× 3 PCS
(500 kcmil
× 3 PCS)
185 mm
2
× 4 PCS
(400 kcmil
× 4 PCS)
300 mm
2
× 4 PCS
(600 kcmil
× 4 PCS)
Maximum cable
size (+/ -/ N)
300mm
2
× 4 PCS
(600 kcmil × 4 PCS)
Содержание DPH-600K
Страница 12: ......
Страница 26: ......
Страница 216: ......
Страница 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 220: ......
Страница 221: ...9 1 9 Maintenance Maintenance...
Страница 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 226: ......
Страница 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 229: ......
Страница 230: ......
Страница 232: ......