6 - 2 4
Modulon DPH Series
8
Go
to
SETUP
ĺ
Mode Setting
ĺ
Frequency Conversion
.
WARNING:
Please note that, once you select '
Frequency Conversion
' mode via the
LCD, the UPS will run in Standby mode and the output will be terminated.
Standby
UPS-1.1
MEASUREMENT
Mode Setting
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
MODE SETTING
On-Line
Green
ECO
Energy
Recycle
Frequency
Conversion
Select to change system mode
10:15
Sep 25,2018
)LJXUH6HOHFW)UHTXHQF\&RQYHUVLRQ0RGH
9
Tap the icon (
UPS-1.1
) located in the upper left corner of the screen to go back to the
Main Screen
.
10
Tap the ON/ OFF Button (
) and the following screen will pop up to ask if you want
to power on the UPS’s inverter. Please select '
YES
'.
Standby
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
POWER ON ?
No
Yes
LOG IN
Administrator
10:15
Sep 25,2018
)LJXUH3RZHURQ5HPLQGHU6FUHHQ
11
After selection of '
YES
' to start up the UPS’s inverter, each power module will start
up and perform self-inspection. After the self-inspection is completed, the UPS will
automatically transfer to run in Frequency Conversion mode and the output frequency
will be the same as setup value. Now, the tri-color LED indicator illuminates green and
the following screen appears.
Содержание DPH-600K
Страница 12: ......
Страница 26: ......
Страница 216: ......
Страница 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 220: ......
Страница 221: ...9 1 9 Maintenance Maintenance...
Страница 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 226: ......
Страница 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 229: ......
Страница 230: ......
Страница 232: ......