3 - 3
3 Operation Modes
3.1.2 Battery Mode_ Single Input_ Single Unit
The UPS transfers to Battery mode automatically if the main AC source is abnormal, for
example, when unstable voltage or a power outage occurs. In Battery mode, the batteries
provide DC power and the UPS converts it into AC power and supplies it to the connected
critical loads via the Output Switch (Q4). During the conversion process, output voltage
remains the same. Please see
)LJXUH
for Battery mode diagram. During Battery mode,
the UPS’s tri-color LED illuminates yellow and the text '
Battery
' appears in the upper right
corner of the screen.
MAIN
LOAD
Q1
Q2
Q4
Q3
Batteries
Rectifier
Inverter
Static Switch
Q5
)LJXUH%DWWHU\0RGH'LDJUDPB6LQJOH,QSXW6LQJOH8QLW
3.1.3 Bypass Mode_ Single Input_ Single Unit
When the inverter encounters abnormal situations such as over temperature, overload,
short circuit, abnormal output voltage or low battery, it will automatically shut itself down.
If the UPS detects the bypass AC source is normal, it will automatically switch to Bypass
mode to protect the connected critical loads from power interruption. Please refer to
)LJXUH
. After the above-mentioned abnormalities are eliminated, the UPS will switch back to
On-Line mode from Bypass mode. During Bypass mode, the UPS’s tri-color LED illuminates
yellow and the text '
Bypass
' appears in the upper right corner of the screen.
MAIN
LOAD
Q1
Q2
Q4
Q3
Batteries
Rectifier
Inverter
Static Switch
Q5
)LJXUH%\SDVV0RGH'LDJUDPB6LQJOH,QSXW6LQJOH8QLW
Содержание DPH-600K
Страница 12: ......
Страница 26: ......
Страница 216: ......
Страница 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 220: ......
Страница 221: ...9 1 9 Maintenance Maintenance...
Страница 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 226: ......
Страница 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 229: ......
Страница 230: ......
Страница 232: ......