5 - 2
Modulon DPH Series
5.1 Before Installation and Wiring
y
Please read this user manual thoroughly before installation, wiring and operation. Only
authorized Delta engineers or service personnel can perform installation, wiring, panel
& cover removal, maintenance and operation. If you want to execute any action men-
tioned above by yourself, the action must be under the supervision of authorized Delta
engineers or service personnel. If you use a forklift or other equipment to move the
836SOHDVHPDNHVXUHLWVORDGEHDULQJLVVXႈFLHQW3OHDVHUHIHUWR
7DEOH
.
y
The UPS must be connected with at least one external battery cabinet (user-supplied,
KDQGOHGDQGFRQ¿JXUHGE\'HOWDVHUYLFHSHUVRQQHO3OHDVHUHIHUWR
([WHUQDO%DW
-
WHU\&DELQHW&RQQHFWLRQ:DUQLQJV
for relevant information.
5.2 Installation
Environment
y
Install the UPS indoors. Do not place it outdoors.
y
Make sure that transportation routes (e.g. corridors, door gates, elevators, etc.) and
installation area can accommodate and bear the weight of the UPS, external battery
cabinet(s), and handling equipment. Please refer to
7DEOH
IRUÀRRUZHLJKWORDGLQJ
information.
Table 5-1: UPS Floor Weight Loading Table
DPH Series UPS_ 200/ 300/ 400/ 500/ 600kVA
UPS Net Weight (without Power Modules): 605 kg (1333.8 lb)
UPS Weight Loading (without Power Modules): 458.3 kg/m
2
(93.9 lb/ft
2
)
UPS
Capacity
200kVA/
200kW
300kVA/
300kW
400kVA/
400kW
500kVA/
500kW
600kVA/
600kW
Power
Module
Q’ty
4
6
8
10
12
Weight
753 kg
(1660.1 lb)
828 kg
(1825.4 lb)
902 kg
(1988.6 lb)
976 kg
(2151.7 lb)
1050 kg
(2314.9 lb)
Floor
Weight
Loading
570.5 kg/m
2
(116.8 lb/ft
2
)
627.3 kg/m
2
(128.5 lb/ft
2
)
683.3 kg/m
2
(140.0 lb/ft
2
)
739.4 kg/m
2
(151.4 lb/ft
2
)
795.5 kg/m
2
(162.9 lb/ft
2
)
y
The UPS allows cable entry from the top or bottom. Please leave adequate space on
the top or at the bottom of the UPS to allow cable entry.
y
Ensure that the installation area is big enough for maintenance and ventilation. Since
the UPS adopts the design of air inlet at the front and air outlet at the rear (see
)LJXUH
5-1
) and the external battery cabinet must be placed next to the UPS, we suggest that
you:
Содержание DPH-600K
Страница 12: ......
Страница 26: ......
Страница 216: ......
Страница 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 220: ......
Страница 221: ...9 1 9 Maintenance Maintenance...
Страница 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 226: ......
Страница 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 229: ......
Страница 230: ......
Страница 232: ......