4 - 4
Modulon DPH Series
4.1.1 Display Port
Before shipment, the display port has been connected to the 10” touch panel with the
designated cable in Delta factory.
4.1.2 REPO Dry Contacts
The REPO dry contacts provide you with quick and convenient interfaces to shut down the
UPS safely when an emergency occurs. Connect the REPO dry contacts to a user-supplied
switch and you can remotely shut down the UPS. The REPO dry contacts provide normally
open (NO) and normally closed (NC) these two options for use.
REPO
NC NO
UPS
5V
1
2
3
4
Buffer
Buffer
NO
NC
5V
)LJXUH5(32'U\&RQWDFWV 6FKHPDWLF
NOTE:
If you want to enable the normally closed (NC) function, please take out the dry
contact card (see
)LJXUH
) and remove its Jump CNR3 (see
)LJXUH
) before
you turn on the UPS.
DISPLAY
REPO
NC NO
EXT. BATT
TEMP.
BT1 BT2
EXT.SWITCH
STATUS
S1
S2
S3
S4
BT3 BT4
O/P DRY
CONTACT
USB
RS-232
P1
P2
P3
P4
P5
P6
I/P DRY
CONTACT
P1
P2
BATT.
START
BATT.
START
P3
P4
PARALLEL
PARALLEL
Screw x 2
Dry Contact Card
)LJXUH/RFDWLRQRIWKH'U\&RQWDFW&DUG
Содержание DPH-600K
Страница 12: ......
Страница 26: ......
Страница 216: ......
Страница 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 220: ......
Страница 221: ...9 1 9 Maintenance Maintenance...
Страница 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 226: ......
Страница 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 229: ......
Страница 230: ......
Страница 232: ......