6 - 3 6
Modulon DPH Series
%\SDVV0RGH7XUQRႇ3URFHGXUHV
WARNING:
1. For parallel units, ensure that every operation procedure mentioned below is
synchronized to all parallel UPSs.
)RUSDUDOOHODSSOLFDWLRQLI\RXMXVWZDQWWRRSHUDWHDVSHFL¿F836EXWQRWDOO
parallel ones, please contact service personnel.
1
In Bypass mode, the LCD shows the following screen (
)LJXUH
and the tri-color
LED indicator illuminates yellow.
Bypass
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
User
Power Flow
Summary
EMS
System Status
10:15
Sep 25,2018
)LJXUH%\SDVV0RGH6FUHHQ
2
Switch
OFF
the Input Switch (Q1), Bypass Switch (Q2) and Output Switch (Q4). After
that, the UPS will run in Standby mode.
3
1RZHDFKSRZHUPRGXOHSHUIRUPV'&%86GLVFKDUJLQJDQGLWV/('LQGLFDWRUÀDVKHV
JUHHQ$IWHUGLVFKDUJLQJHDFKSRZHUPRGXOH¶V/('LQGLFDWRUZLOOEHRႇ
4
About 3 minutes later, the UPS will shut down, and the LCD and tri-color LED indicator
ZLOOEHRႇ
5
Switch
OFF
every external battery cabinet’s breaker (Q5).