5 - 3 6
Modulon DPH Series
5.7.3 STS Module’s LED Indicator
The STS module’s LED indicator shows its operation status. Please refer to the following
table.
(STS Module Left Side View)
LED
Indicator
)LJXUH/RFDWLRQRIWKH6760RGXOH¶V/(',QGLFDWRU
LED Indicator
Description
OFF
The STS module is OFF.
ON (yellow)
The STS module is working in bypass mode,
ECO mode, or energy recycle mode.
Flashing (yellow)_ on for 0.3
VHFRQGDQGRႇIRUVHFRQGV
The STS module is abnormal.
NOTE:
In bypass mode, if you turn the STS module’s switch to the lower position (
), the
676PRGXOHZLOOVKXWGRZQLWVRXWSXWDQGLWV/('LQGLFDWRUZLOOEHRႇ
5.8 Power Module (Optional)
The power module is optional (not included in the package of the UPS). It is hot swappable
and each capacity is 50kVA/ 50kW. Please follow your UPS capacity to install the correct
number of power modules. Please refer to the table below.
UPS Capacity
200kVA/
200kW
300kVA/
300kW
400kVA/
400kW
500kVA/
500kW
600kVA/
600kW
Power Module Q’ty
4
6
8
10