7 - 4 6
Modulon DPH Series
On-Line
1
2
3
4
Security
Leakage
Fire
Smoke
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
MEASUREMENT
EMS Setting
10:15
Sep 25,2018
EMS SETTING
INPUT
CONTACT
SENSOR
ID 0
EMS0
Title
ID
Status
Disable
Input
Contact
NO/NC
Title
Event Type
Normally Open
Normally Open
Normally Open
Normally Open
Warning
Warning
Warning
Warning
NOTE:
After connecting the optional EMS 1000 (EnviroProbe) to the UPS, you have to
manually set both
ID
and
Status
to enable the EMS function of the UPS. Settings
for the other items can be adjusted according to your needs; the default values are
VKRZQLQWKH¿JXUHVDERYH
All the settings in the table below are related to the items shown on the
EMS
screen in the
MEASUREMENT
ĺ
EMS
. Please refer to
(06
.
Item
Sub Item
Description
SENSOR
ID
Set the ID # (ID 0/ ID 1/ …/ ID 15) according to the ID DIP
switch setting of the EMS 1000 (EnviroProbe) device.
NOTE:
If the ID # setting is wrong, the warning message
'
The EMS 1000 ID # Communication Fail
' will
appear.
Title
Set the title for each EMS 1000 (EnviroProbe) device.
Status
The status
Enable
/
Disable
determines whether or
not the LCD shows the information of the EMS 1000
(EnviroProbe) device (ID #) on the screen.
Temperature
Set the temperature (°C) values for Alarm/ Warning/
Recovery.
Humidity
Set the humidity (%) values for Alarm/ Warning/ Recovery.
Содержание DPH-600K
Страница 12: ......
Страница 26: ......
Страница 216: ......
Страница 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 220: ......
Страница 221: ...9 1 9 Maintenance Maintenance...
Страница 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 226: ......
Страница 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 229: ......
Страница 230: ......
Страница 232: ......