5 - 2 3
5 Installation and Wiring
UPS 1
UPS 2
UPS 8
3Ø4W
3Ø4W
3Ø4W
Main AC Source
Bypass AC Source
Loads
AC Input
Terminals
Bypass Input Terminals
Bypass Input Terminals
Bypass Input Terminals
AC Input
Terminals
AC Input
Terminals
UPS Output
Terminals
Parallel Port
Parallel Port
Parallel Port
Parallel Port
Parallel Port
Parallel Port
UPS Output
Terminals
UPS Output
Terminals
Parallel Cable
Parallel Cable
Parallel Cable
Daisy
Chain
Method
)LJXUH3DUDOOHO8QLWV'XDO,QSXW:LULQJ'LDJUDP
NOTE:
For dual input, the UPS will not work normally if the main AC power’s
QHXWUDO1DQGE\SDVVSRZHU¶VQHXWUDO1DUHQRW¿UPO\FRQQHFWHGRUQRW
connected to the AC Input neutral (N) terminal shown in
)LJXUH
.
4
Use the provided parallel cables*
1
to connect the parallel ports of the parallel units.
Please adopt the Daisy Chain method shown in
)LJXUH
. For the parallel
port location, refer to
)LJXUH
.
NOTE:
*
1
One parallel cable is provided in each UPS’s accessory package.
5
Follow
)LJXUH
to ground the parallel UPS units, external battery cabinet(s)
and connected critical loads.
WARNING:
%HIRUHVWDUWXSRIWKHSDUDOOHOXQLWVTXDOL¿HGVHUYLFHSHUVRQQHOPXVWVHW
each UPS’s '
Parallel Group ID
' (1 or 2) and '
Parallel ID
' (1 ~ 8) through
the LCD. Otherwise, the parallel UPSs cannot be started. Please refer to
3DUDOOHO6HWWLQJ
.
Содержание DPH-600K
Страница 12: ......
Страница 26: ......
Страница 216: ......
Страница 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 220: ......
Страница 221: ...9 1 9 Maintenance Maintenance...
Страница 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 226: ......
Страница 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 229: ......
Страница 230: ......
Страница 232: ......