6 - 2 8
Modulon DPH Series
10
Tap the ON/ OFF Button (
) and the following screen will pop up to ask if you want
to power on the UPS's inverter. Please select '
YES
'.
Bypass
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
POWER ON ?
No
Yes
LOG IN
Administrator
10:15
Sep 25,2018
)LJXUH3RZHURQ5HPLQGHU6FUHHQ
11
After selection of '
YES
' to start up the UPS’s inverter, each power module will start
up and perform self-inspection. At the same time, the system begins synchronization
with the bypass AC source. After the self-inspection is completed, the UPS will
automatically transfer to run in Green mode and the system will automatically detect
WKHRXWSXWVWDWXVLHWRWDOORDGFDSDFLW\WRGHFLGHZKLFKVSHFL¿FSRZHUPRGXOHV
VKRXOGEHIXOO\SRZHUHGRQRULGOHLQRUGHUWRDFKLHYHKLJKHUHႈFLHQF\RIWKH836
Now, the tri-color LED indicator illuminates green and the following screen appears.
Green
POWER FLOW
Maintenance
Bypass
Bypass
Mains
90 %
5 mins
Load
30 %
MEASUREMENT
Power Flow
UPS-1.1
SETUP
MAINTENANCE
EVENT LOG
LOG IN
Administrator
Power Flow
Summary
EMS
System Status
10:15
Sep 25,2018
)LJXUH*UHHQ0RGH6FUHHQ
Содержание DPH-600K
Страница 12: ......
Страница 26: ......
Страница 216: ......
Страница 217: ...8 1 8 Optional Accessories 8 Optional Accessories...
Страница 220: ......
Страница 221: ...9 1 9 Maintenance Maintenance...
Страница 223: ...A1 1 Appendix 1 7HFKQLFDO 6SHFL FDWLRQV Technical 6SHFL FDWLRQV A1 A1...
Страница 226: ......
Страница 227: ...A2 1 Appendix 2 Warranty Warranty A2 A2...
Страница 229: ......
Страница 230: ......
Страница 232: ......